3.2 Commands Details

3-31

3

Commands for Preparation Process

3.2.18 Monitor and Adjust Settings (ADJ: 3EH)

Send an ADJ command to monitor and adjust settings.

(1) ADJ Command (3EH)

The specifications of the ADJ command are described below.

(2) How to Send an ADJ Command for Adjustment

The table below lists the adjustments that can be executed by sending an ADJ command.

Byte

ADJ

Description

Command

Response

1

3EH

3EH

Phases in

which the

command can

be executed

Phase 2 and 3

Synchronization

classification

Asynchronous

command

2

SUBCODE=01

ALARM

Processing

time

Depends on pro-
cessing

Subcommand

Cannot be used

3

STATUS

• Use this command as SUBCODE = 01H.

The SERVOPACK will be in maintenance mode.

And, data monitoring and adjustment will be enabled.

• See (2) How to Send an ADJ Command for Adjustment for details on

ADJ for adjustment.

• See (3) How to Send an ADJ Command for Monitoring Data for details

on ADJ for monitoring data.

• A warning will occur and the command will be ignored in the following

cases.
- While editing using SigmaWin or digital operator: Command warning

1 (A.95A)

- CADDRESS is out of the range: Parameter setting warning 1 (A.94A)
- CSIZE does not match: Parameter setting warning 4 (A.94D)
- CCMD and/or CDATA are out of the range: Parameter setting warning

2 (A.94B)

4

5

CCMD

CANS

6

7

CADDRESS

CADDRESS

8

9

CSIZE

CSIZE/

ERRCODE

10

11

CDATA

RDATA

12

13

14

15

16

WDT

RWDT

List of Executable Adjustments

Adjustment

Request

Code

Preparation

Before

Execution

Processing

Time

Execution Conditions

Normal mode

0000H

None

200 ms max.

Parameter initialization

1005H

None

20 s max.

Initialization is impossible while the servo
is ON.
After initialization, the power supply must
be turned OFF and then ON again.

Absolute encoder reset

1008H

Required

5 s max.

When using an incremental encoder, it is
impossible to reset the encoder while the
servo is ON.
After initialization, the power supply must
be turned OFF and then ON again.

Automatic offset adjustment
of motor current detection sig-
nals

100EH

None

5 s max.

Adjustment is disabled:

• While the main circuit power supply is

OFF

• While the servo is ON
• While the servomotor is running