7 Data Field

7.2.1 Substatus Field Specification

7-10

7.2 Substatus Data Field

7.2.1 Substatus Field Specification

The substatus field is used to monitor status of subcommands.

• Substatus Field

7.2.2 Extension Status Field Specifications

This field is used to monitor extension status.

The SMON, LTMOD_ON, and LTMOD_OFF subcommands can be used to enable monitoring.

• L_CMP_CNT (D0-D7)

This counter indicates how many times the latch sequence has been completed during continuous latch oper-
ation. It remains 0 during a normal latch operation.

• L_SEQ_NO (D8-D11)

This number indicates the number of latch sequence being completed during a continuous latch operation. It

remains 0 during a normal latch operation.

Byte

18

D7

D6

D5

D4

D3

D2

D1

D0

Reserved

Reserved

Reserved

Reserved

Reserved

SBCM-

DRDY

SBWARNG

SBALM

Bit

Name

Description

Value

Status

D0

SBALM

Subcommand alarm occurs.

0

No alarm

1

Alarm occurs

D1

SBWARNG

Subcommand warning occurs.

0

No warning

1

Warning

D2

SBCMDRDY

Subcommand Ready

(Subcommand can be received)

0

Busy

1

Ready

Byte

28

D7

D6

D5

D4

D3

D2

D1

D0

L_CMP_CNT

Byte

29

D15

D14

D13

D12

D11

D10

D9

D8

L_SEQ_NO