Setting the communications specifications – Yaskawa Sigma-5 User Manual: MECHATROLINK-II Commands User Manual

Page 23

Advertising
background image

2 Operation Sequence

2.1.1 Setting MECHATROLINK-II Communications

2-6

(3) When the Large-Capacity

Σ-V Series SERVOPACKs (SGDV-†††H11,

-†††J11) are Used

The rotary switch (S2) and DIP switch (S3), which are located near the top under the plastic cover of the SER-

VOPACK, are used as shown below to set the MECHATROLINK-II communications specifications.

„

Setting the Communications Specifications

Set the communications specifications using the DIP switch (S3).

4

3

5

2

6

1

7

C

8

0

F

9

E

A

D

B

ON

OFF

1

2

3

4

S3

S2

S3

Function

Setting

Description

Factory setting

Pin 1 Sets the baud rate.

OFF

4 Mbps (MECHATROLINK-I)

ON

ON

10 Mbps (MECHATROLINK-II)

Pin 2

Sets the number of

transmission bytes.

OFF

17 bytes

ON

ON

32 bytes

Pin 3 Sets the station address.

OFF

Station address = 40H + S2

OFF

ON

Station address = 50H + S2

Pin 4 Reserved. (Do not change.)

OFF

OFF

• When connecting to a MECHATROLINK-I network, turn OFF pins 1 and 2.
• When using a MECHATROLINK-I network (Baud rate: 4 Mbps), the settings for the

number of transmission bytes is disabled and the number of transmission bytes is
always 17.