3 Commands for Preparation Process

3.2.18 Monitor and Adjust Settings (ADJ: 3EH)

3-32

ADJ Command Execution Procedure for Adjustment:

1. Send the following data and set the request code of the adjustment to be executed.

CCMD

= 0004H

CADDRESS =

2000H

CSIZE

= 0002H

CDATA

= Request code of the adjustment to be executed

When the slave station receives the command normally, CMDRDY of status field will be set to 1. Also
check ERRCODE. If an error occurs, carry out the operation in step 4 to abort execution.

2. For adjustment that requires a preparation process, send the following data.

CCMD

= 0004H

CADDRESS =

2001H

CSIZE

= 0002H

CDATA

= 0002H

When the slave station receives the command normally, CMDRDY of status field will be set to 1. Also

check ERRCODE. If an error occurs, carry out the operation in step 4 to abort execution.

3. Send the following data to execute adjustment.

CCMD

= 0004H

CADDRESS =

2001H

CSIZE

= 0002H

CDATA

= 0001H

When the slave station receives the command normally, CMDRDY of status field will be set to 1. Also

check ERRCODE. If an error occurs, carry out the operation in step 4 to abort execution.

4. Send the following data to abort the execution.

CCMD

= 0004H

CADDRESS =

2000H

CSIZE

= 0002H

CDATA

= 0000H

When the execution is aborted, CMDRDY of status field will be set to 1.

Note: If a communications alarm (A.E50 or A.E60) occurs after the request code has been set and before adjustment has

been executed, the adjustment can not be carried out. Remove the cause of the alarm and restart the adjustment pro-
cedure.

Multiturn limit setting

1013H

Required

5 s max.

When using an incremental encoder, the set-
ting is disabled unless A.CC0 (Multiturn
limit disagreement) occurs.
After initialization, the power supply must
be turned OFF and then ON again.

Details of Command for Adjustment

Command

Response

CCMD/CANS

CCMD = 04H

CANS = 04H (copy of the command)

CADDRESS

Setting address

Reference address (copy of the command)

CSIZE/
ERRCODE

2 or 4

At normal reception: 0000H
At error occurrence: A value other than 0

CDATA/RDATA

Setting data

Setting data (copy of the command)

List of Executable Adjustments (cont’d)

Adjustment

Request

Code

Preparation

Before

Execution

Processing

Time

Execution Conditions