22 (2) soft start function, 3) torque (force) reference option – Yaskawa Sigma-5 User Manual: MECHATROLINK-II Commands User Manual

Page 87

Advertising
background image

4 Motion Commands for Operation

4.2.10 Velocity Control (VELCTRL: 3CH)

4-22

(2) Soft Start Function

The soft start function converts input speed references from sudden step progression to steady diagonal pro-

gression. Set the acceleration speed and deceleration speed in the following parameters.

Use this function to achieve a smooth speed control in speed control mode (excluding internal set speed selec-

tion).

Note: For normal speed control, set Pn305 and Pn306 to 0 (factory setting).

(3) Torque (Force) Reference Option

The settings of the parameters related to the torque (force) reference option for VELCTRL command are listed

below.

Pn305

Soft Start Acceleration Time: Time of period the motor speed reaches the maximum from zero

(the stop status)

Setting Range

Unit

Factory Setting

When Enabled

0 to 10000

1 ms

0

Immediately

Pn306

Soft Start Deceleration Time: Time of period the motor speed decreases to zero (stop status) from

the maximum.

Setting Range

Unit

Factory Setting

When Enabled

0 to 10000

1 ms

0

Immediately

Before soft-start

After soft-start

Max. motor speed

Pn305

Pn306

Parameter

Description

Pn002

n.†††0

The set values of P_TLIM and N_TLIM are invalid. (factory setting)

n.†††1

Uses the set value of P_TLIM/N_TLIM as forward/reverse torque (force) limit.

n.†††2

Uses TFF as the torque (force) feed forward. Set N_TLIM to 0.

n.†††3

When P_CL of OPTION field is set to 1, uses P_TLIM as the torque (force) limit.
When N_CL of OPTION field is set to 1, uses N_TLIM as the torque (force) limit.