Installation requirements, Installation requirements -27 – Alcatel Carrier Internetworking Solutions Omni Switch/Router User Manual

Page 57

Advertising
background image

Connecting a DC Power Source to an OmniS/R-PS9-DC725

Page 1-27

Connecting a DC Power Source to an
OmniS/R-PS9-DC725

The OmniS/R-9P can use a DC power supply called the OmniS/R-PS9-DC725. This power
supply contains a female power connector as shown in the figure below. This supply requires
the use of 10 gauge wire. A clamp inside each connector keeps the power wire tightly in
place during operation.

OmniS/R-9P DC Power Supply Connector Style

Installation Requirements

Caution: To reduce the risk of electric shock or energy hazards:

• The branch circuit overcurrent protection must be rated at a minimum of 30 A (amperes)

for the OmniS/R-9P PS9-DC725.

• Use 10 gauge (AWG - American Wire Gauge) solid copper conductors only for the

OmniS/R-9P PS9-DC725.

• A readily-accessible disconnect device that is suitably approved and rated shall be incorpo-

rated in the field wiring.

• This device is to be installed in a restricted access area in accordance with the NEC

(National Electrical Code) or the authority having jurisdiction.

• Connect this device to a reliably grounded SELV (Safety Extra Low Voltage) or a central-

ized DC source.

GND =

GND/(+)/(-)

OmniS/R-PS9-DC725