10 shutdown wait time administration, 11 dual power feed administration, Shutdown wait time administration 4–19 – FUJITSU SPARC M4000 User Manual

Page 227: Dual power feed administration 4–19, Section 4.4.10

Advertising
background image

Chapter 4 Operation of the Server

4-19

4.4.10

Shutdown Wait Time Administration

The shutdown wait time administration is a setting to delay the shutdown start by
specifying the shutdown start time when a power failure has occurred in the system
with the UPS.

Command operation

1. Use the showshutdowndelay (8) command to display the shutdown wait time.

XSCF> showshutdowndelay

UPS shutdown wait time : 500 second(s)

2. Use the setshutdowndelay (8) command to set the shutdown wait time. Set

the shutdown wait time from 0 to 9999 (sec). The default is "10 sec."

<Example> The shutdown wait time is set to 600 sec.

XSCF> setshutdowndelay -s 600

4.4.11

Dual Power Feed Administration

The dual power feed is a type of power feed for high-reliability systems that contain
dual lines to the power supply. If one line has stopped, the other line does not stop
and enables the system to continue operation. The dual power feed is enabled and
disabled by an XSCF Shell command. This setting is done by FEs.

Note –

Enabling and disabling the dual power feed is the setting for only midrange

systems. In high-end systems, the dual power feed is optional. If you use the option,
the dual power feed is enabled.

Command operation

1. Use the showdualpowerfeed (8) command to display the current setting

status of the dual power feed.

XSCF> showdualpowerfeed

Dual power feed is disabled.