FUJITSU SPARC M4000 User Manual
Page 228

4-20
SPARC Enterprise Mx000 Servers XSCF User’s Guide • April 2008
2. Use the setdualpowerfeed (8) command to enable or disable the dual power
feed of this system.
<Example 1> Enabling the dual power feed.
XSCF> setdualpowerfeed -s enable
disable -> enable
NOTE: Dual power feed will be enabled the next time the platform
is powered on.
<Example 2> Disabling the dual power feed.
XSCF> setdualpowerfeed -s disable
enable -> disable
NOTE: Dual power feed will be disabled the next time the platform
is powered on.
3. Confirm the new setting, and if it is correct, execute the rebootxscf (8)
command to reset the XSCF.
XSCF> showdualpowerfeed
disable -> enable
NOTE: Dual power feed will be enabled the next time the platform
is powered on.
4. Confirm whether the setting is valid after resetting the XSCF the next time.
XSCF> showdualpowerfeed
Dual power feed is enabled.