Nev 300 lsn power supply – Bosch 8-Dec User Manual

Page 116

Advertising
background image

108 | Accessories for Control Panels and Keypads | Power Supplies and Batteries

NEV 300 LSN power supply

Features

Can be connected to all LSN control panels (centralized

or decentralized)

A maximum of two 12 V/17 Ah batteries can be used
Monitoring of mains and battery voltage
Tamper protection (tamper contact)
3 freely programmable open collector outputs
Slot for optional voltage converter (to 28 V)

The NEV 300 LSN is an additional power supply for LSN
control panels.

System Overview

This additional power supply for LSN control panels is
connected to the LSN local security network in an LSN loop
or in max. 2 LSN stubs.

1

LSN control panel

2

LSN element

3

Connection in an LSN loop or in up to 2 LSN stubs

Functions

Control assembly:

230 V mains supply

Power failure protection, transformer connection,

rectifier

Battery charge control and monitoring

Battery check

Voltage surge protection

Fault recognition and display

Connector board

LSN lines with power supply connection

Battery connection

External user connection

Slot for 28 V voltage converter

Fuses for voltage outputs

3 open collector outputs (C points), 2 relay modules can

be plugged in if needed

The power supply is a separate LSN element and is
programmed from the control panel with the corresponding
program. Message types such as tampering with tamper
contacts and power supply or battery faults are transmitted
to the control panel via LSN.
The battery charge voltage is set at the factory. The
controller and the internal temperature sensor ensure
temperature-adjusted battery charging. A remote PTK
tracker can be used if needed. Should readjustment be
necessary, this is carried out via a potentiometer on the
control assembly.
The battery monitor identifies when voltage falls below
discharge level, interruption and short-circuit of the battery
cable. The test cycle can be set to 1 min. or 15 mins. The
battery load test lasts for 2 seconds and is switched off if
the regulator is inoperative (power failure).
Device display
The display visible from the outside contains the operating
indicator (green LED) that is lit when the battery and/or
230 V is connected, and the power supply failure indicator
(yellow LED) that is lit when a battery and/or mains fault
occurs.

Certifications and Approvals

Region

Certification

Europe

CE

NEV 300 LSN

Germany

VdS

G 103030, C NEV 300 LSN

Installation/Configuration Notes

The energy balance is determined according to

VDE 0833 and created using the "uezpro" planning and

current calculation program. The limits are calculated

automatically. Any external peripheral devices

connected must be included in the calculation.

Current consumption at 12 V; 1.2 A per connection

point

Bosch Security Systems B.V.

www.boschsecurity.com

2