336 | LSN Peripherals | LSN Smoke

Region

Certification

Europe

CE

FAP-520 / FAA-500-R

CPD

0786-CPD-20201 FAP-O 520 / 520-P
0786-CPD-20202 FAP-OC 520 / 520-P

Germany

VdS

G 205125 FAP-O 520/520-P
G 205119 FAP-OC 520/520-P

Poland

CNBOP

2565/2007 FAP-O 520, FAP-O 520-P
2566/2007 FAP-OC 520, FAP-OC 520-P

Hungary

TMT

TMT-20/2006 FAP-O 520, FAP-O 520-P
TMT-21/2006 FAP-OC 520, FAP-OC 520-
P

Russia

GOST

POCC DE.C313B06300

Installation/Configuration Notes

Can be connected to the Modular Fire Panel FPA‑5000

with the improved LSN system parameters

in "Classic Mode" can be connected to the LSN fire

panels BZ 500 LSN, UEZ 2000 LSN, UGM 2020 and to

other panels or their receiver modules with identical

connection conditions, although with the previous LSN

system parameters

The detectors and detector bases can be used together

with the „Rotaris“ lamp by Philips.

The detectors must be installed exclusively in the

FAA‑500 LSN Bases provided. In addition, the detector

base must be installed in an FAA‑500‑BB Ceiling Mount

Back Box or in an FAA‑500‑SB Surface Mount Back Box.

Note

For flush ceiling mounting with FAA‑500‑BB:
The false ceiling may have a maximum
thickness of 32 mm. Above the false ceiling, a
free height of at least 110 mm is required.

The detectors are not intended for outdoor use.

A hemispherical space with a radius of 50 cm must

remain free below the detectors.

1

Detector

2

Ceiling

3

Hemispherical space below the detector

Care must be taken to ensure that neither people, large

animals, plants, swinging doors nor any objects intrude

into this area and that no parts of the detector surface

become covered.

The detectors may only be installed in a position which

is out of arm's reach. We therefore recommend a

minimum installation height of 2.70 m.

The detectors may not be installed in rooms in which

data is transmitted by means of high-intensity infrared

light (e g. in rooms with IR systems for interpreters).

The detectors must be mounted so that they are not

exposed to any direct sunlight.

A minimum distance of 50 cm from lamps must be

maintained. The detectors may not be mounted in a

cone of light from lamps.

The bases are equipped as standard with a spring which

is suitable for installation of the detector in false

ceilings. When the detector is installed in concrete or

wooden ceilings, these need to be replaced by the

stronger springs FAA‑500‑SPRING with red markings.

Maximum permitted air speed: 20 m/s

Country-specific standards and guidelines must be

observed during the planning phase.

Installation/configuration notes in accordance with VdS/

VDE

In accordance with VDE, only 127 detectors may be

connected to the loop, while only 32 automatic or

10 manual detectors may be connected in the stub.

The FAP‑OC 520, like the FAP‑O 520, is planned

according to the guidelines for optical detectors (see

DIN VDE 0833 Part 2 and VDS 2095).

Parts Included

Detector type

Qty.

Components

FAP-O 520

1

Optical Smoke Detector, White

FAP-O 520-P

1

Optical Smoke Detector, Transparent with Col-

or Inserts

FAP-OC 520

1

Multisensor Detector Optical/Chemical, White

FAP-OC 520-P

1

Multisensor Detector Optical/Chemical, Trans-

parent with Color Inserts

Technical Specifications

Electrical

Operating voltage

15 V DC . . 33 V DC

Current consumption

< 3.26 mA

Alarm output

Per data word by two-wire signal line

Indicator output

Open collector connects 0 V over 1.5 kΩ

through, max. 15 mA

Mechanics

Dimensions

Detector

Ø 113 x 55 mm

Detector with Tim Ring

Ø 150 x 55 mm

Detector with Trim Ring,

Base and Ceiling Mount

Back Box

Ø 150 x 110 mm

Housing material

Polycarbonate

Color

Detector housing

Signal white, RAL 9003

Detector front plate

FAP‑O 520/ FAP‑OC 520

signal white matt

Detector front plate

FAP‑O 520‑P/

FAP‑OC 520‑P

transparent/silver-gray

Weight

Without / with packaging

Bosch Security Systems B.V.

www.boschsecurity.com