Bosch 8-Dec User Manual

Page 68

Advertising
background image

60 | Control Panels, Control Centers, and Keypads | UEZ 2000

Message display and operation
The integrated operating unit (ADT) or a remote operating
panel can be used to process incoming messages and
operate the system.
Saving messages
A log printer can be integrated to record messages. Up to
1000 events can be stored in an event database.
System loop technology (SRT)

Up to 6 control panels in one SRT loop (UEZ 2000 and/

or UEZ 2000)

Central or decentralized assignment as required

Cost-effective networking using standard cabling (4-

wire) up to 1000 m

Greater coverage via modem or fiber optic cable

High level of operating reliability through fault-tolerant

operation in the event of a line short-circuit or

interruption

Malfunction message reported to all systems to aid in

malfunction localization

One or more transmitters can be integrated into the

cluster as required

All information is available at each control panel

Complete simultaneous operation is possible and

permitted on all control panels

Up to 508 detector zones

Up to 2032 LSN elements

Built-in operating panel and printer (optional) per

control panel

Up to 4 remote BE 1000 operating panels per control

panel

Encrypted data transmission in the SRT loop

Up to 48 LSN loops or 96 stubs or a combination of both

with the UEZ 2000 LSN SRT

Additional function with the UEZ 2000 LSN
The UEZ 2000 LSN can also be equipped with an additional
LVM 100. This increases the connection potential to 8 loop
or 16 stub lines and/or a max. of 508 connectable LSN
elements.

Certifications and Approvals

Region

Certification

Europe

CE

UEZ 2000 LSN
UEZ 2000 LSN A2

Germany

VdS-S

S 184507, B NMZ 300 H
S 196602, B NMZ 1000 B
S 196001, C NMZ 1000 C
S 17370, C NMZ 300

VdS

G 197009, C UEZ 2000 N

Installation/Configuration Notes

One-man test

Automatic service request in the event of detector

contamination

127 detector zones

99 detectors per detector zone (not VdS)

32 detector area

5 fixed and 19 variable control panel C points

Internal and external expansion options

Components

Number Short description

Internal extension
SEMO1

1

Module with 2 serial interfaces and SEZU

(encrypted data transmission)

AT 2000

1

Dial-up modem for transmitting informa-

tion via the telephone network to a moni-

toring station and/or TeleService

DIP

1

Switching an internal program on or off

from multiple independent points

NRK-N

2

For 230 V switching outputs; C point ac-

tivation

TRSP

1

Integration of up to 5 x TRN

SIV

1

For additional monitored protection of

users connected to the UEZ 2000 LSN

LSA+

1

Additional connection strip

ASE

1

For connecting 2 x 2 BES in parallel, can

be plugged into AVM 100

TRN

6

For zero-potential outputs of control pan-

el functions; can be plugged into AVM 100

RTP

6

For zero-potential outputs of 4 control

panel functions each; can be plugged into

AVM 100

SM 20

5

Interface module for 20 mA interface; for

connecting a printer, UGM 2020, RUBIN

2020NT or BoVis NT

SM24

3

Interface module for V.24 interface; for

connecting UGM 2020, RUBIN 2020NT,

Bovis NT or SRT

SM 485

1

Interface module for RS-485 interface,

for connecting 4 x BE 1000

Printer

1

Message logging

ATE 100 LSN

1

Parallel display of 32 detector zones (can

be installed in operating panel)

Key switch

8

or 1

and 6

With 2 activation settings

With 3 switch setting options (1-0-2) in

the operating panel

With 2 switch settings

12 V/10 Ah battery 2

Uninterrupted power supply (UPS) to the

system

External extension
External signaling

device

8

Up to 8 independently activated BESs can

be connected via ASE and NSB 100

ATBL

8

For connecting remote display panels,

each with 64 outputs

Transmission equip-

ment (VdS)

1

For transmitting emergency call alarms to

a receiving center

SD

1

Connection is made at the AVM 100

UEV 1000

1

For additional energy requirements; con-

tains one 12 V/5.4 A power supply unit

and 2 12 V/40 Ah batteries

Bosch Security Systems B.V.

www.boschsecurity.com

1

Advertising