76 | Accessories for Control Panels and Keypads | Expansion Modules
Parts Included
Quantity Component
1
Single-zone input module
1
Literature pack
Technical Specifications
Circuit Parameters
Initiating Circuit Type (DS7457iF):
Class B (Style A)
Signaling Line Circuit Type:
Class B (Style 4)
Environmental Considerations
Temperature (Operating):
0°C to +49°C (+32°F to +120°F)
Power Requirements
Current Draw:
0.5 mA maximum
Voltage (Operating):
8 VDC peak (minimum)
Ordering Information
DS7457i Single Zone Input Module
Connects normally-open (NO) or normally-
closed (NC) contacts, and supervises the con-
tacts using 47 kΩ end-of-line(EOL) resistors.
Designed for intrusion applications.
DS7457i
DS7457iF Single Zone Input Module
Connects normally-open (NO) or normally-
closed (NC) contacts, and supervises the con-
tacts using 47 kΩ end-of-line(EOL) resistors.
Designed for fire applications.
DS7457iF