234 | Detectors and Accessories | Smoke

F220 Heat Detectors

Features

Two-wire or four-wire bases
50 ft (15.2 m) maximum spacing between detectors
Visible identification of model: F220‑135 = no ring,

F220‑135F = gray ring, F220‑190F = black ring

Tamper detection
Dual color LED

The F220 Heat Detectors include:

F220‑135: An electronic rate-of-rise, fixed temperature

heat detector that initiates an alarm when the ambient

temperature exceeds +135°F (+57°C) or when the

ambient temperature increases by +15°F (+8.3°C) or

more in less than 1 minute

F220‑135F: An electronic fixed temperature heat

detector that initiates an alarm when the ambient

temperature reaches +135°F (+57°C).

F220‑190F: An electronic fixed temperature heat

detector that initiates an alarm when the ambient

temperature reaches +190°F (+88°C).

The detectors use low current electronic circuitry, so they
can connect to 12 VDC nominal or 24 VDC nominal power
source circuits. When mounted on the appropriate F220‑B6
Series Mounting Base, the F220 Heat Detectors provide
general property protection from fire.

Warning

Heat detectors are not life safety devices.

Functions

Compatible Bases
Configure the detectors as either two-wire or four-wire
depending on the mounting base selected. These detectors
are compatible with any of the F220‑B6 bases:

F220‑B6 12/24 VDC Two-wire Mounting Base

F220‑B6R Standard 12/24 VDC Four-wire Mounting

Base

F220‑B6RS 24 VDC Four-wire Mounting Base with

Sounder

F220‑B6C 12/24 VDC Four-wire Mounting Base with

Auxiliary Form C Relay

F220‑B6E 12/24 VDC Four-wire Power Supervision

Mounting Base

F220‑B6PM 24 VDC Four-wire Addressable Master Base

F220‑B6PS 12/24 VDC Four-wire Addressable Base

Dual-color LED
To verify the detector has power and the heat detection
circuitry functions, a dual-color LED indicator flashes green
every 8 sec when operating normally. It flashes once every
4 sec when a trouble condition exists. The LED latches on
red if an alarm occurs, allowing the user to easily verify
individual detector alarms. Clear the alarm condition by
interrupting power to the detector.
Tamper Detection
When detector heads are correctly installed in any of the
F220‑B6 bases, the control panel initiates a trouble signal
if a detector is removed from its base. A mechanical tamper
lock comes with each base to inhibit unauthorized head
removal.
Supervision
The control panel supervises two-wire systems. Supervision
of four-wire system power is provided by an end-of-line
(EOL) power supervision device such as a D275, or an
F220‑B6E Power Supervision Mounting Base and an EOL
resistor as specified by the control panel manufacturer.

Certifications and Approvals

Region

Certification

Europe

CE

89/336/EEC, EN50130-4/A Sept 1998,
EN61000-6-3 Oct 2001

USA

UL

UQGS: Heat - Automatic Fire Detectors
(UL521), UQGS7: Heat - Automatic Fire
Detectors Certified for Canada (cULus)

FM
CSFM

7270-1615: 108 July 2008

NYC-MEA

117-05-E

MSFM

2200 Sep 2008

Hong Kong

HKFSD

Installation/Configuration Notes

Compatible Control Panels
Addressable Systems:
compatible with addressable
systems controlled by D9412GV2, D7412GV2, D9412G, or
D7412G Control Panels or the D9124 Fire Alarm Control
Panel when used with the F220-B6PM or F220-B6PS
Addressable Detector Bases.