Msa-lsn c surface-mount magnetic contact – Bosch 8-Dec User Manual

Page 365

Advertising
background image

LSN Peripherals | LSN Magnetic Contacts | 357

MSA-LSN C Surface-Mount

Magnetic Contact

Features

LSN surface-mount magnetic contact
VdS class C
Tamper switch
Parallel or head-on surface mounting
LSN perimeter protection

Magnetic contacts are used for tear-off surveillance of
doors and windows.

Certifications and Approvals

Region

Certification

Europe

CE

MSE/MSA-LSN B/C

Germany

VdS

G 104006, C MSE/MSA-LSN C

Coun-
try

Certification

MSA-LSN C

DE

VdS

G 104006, C

Installation/Configuration Notes

Installation notes

Head-on or parallel surface mounting.

The surface mounting version is implemented via the

AG4 surface mounting housing and enables installation

on ferromagnetic materials.

1

Contact

2

Magnet

3

AG4 surface mounting housing

4

Plastic part

5

Magnet offset in the axial direction

6

Warning! The adjustment mark must point to the magnet.

Connecting LSN contacts

Each LSN contact is a physical LSN element (1 out of

127 possible per loop).

The length of LSN contact connection cables must be

included when planning the total line length of the LSN

loop, as LSN technology is incorporated in these

detectors.

Passive coupling elements for joining the connection

cables to the installation cable must be placed as close

as possible to the LSN contacts. The 1 m connection

cable with 2 m LSN cable length is included in the

calculation of the LSN cable length (LSN is carried into

the contacts and back out again).

Connector boxes (optional) are classified as installation

material.

Testing LSN contacts

Reed switch and microswitch functions can be checked

before installation by a high-Ohm multimeter or

continuity checker (for diode paths).

The resistance values are approximate values; a large

change in resistance is significant here.

1

Detector

2

High-Ohm multimeter

Contact open: approx. 3 megaohm

Contact closed: approx. 1 megaohm

Note

Only the intrusion contact can be checked in
this way. The tamper switch of the Class C
magnetic contact can be checked by the LSN
control panel or with the LSN testing device
(software version 3.x onward).

www.boschsecurity.com

Bosch Security Systems B.V.

6

Advertising