422 | Conettix - Information Transport Solutions | Conettix - AT2000/ATE

Operation using the primary multiplex connection S2M

is not possible.

The AT 2000 TSN ISDN communicator for danger alarms

must be connected to the S

0

bus as the first device.

With this connection, it is possible for the

AT 2000 TSN ISDN to send a message even in the event

of tampering or damage to the bus wiring.

ISDN PTP

The "constant monitoring" layer 1 feature is present by

default for system access.

The max. cable length from network termination NT via

the UAE 8/8 box to the TK system or to the end unit is

1000 m.

ISDN PMP

The "constant monitoring" layer 1 feature is also

required with a multi-system connection.

The max. cable length between network termination

and TK system or end unit is 150 m.

GSM transmission

The GSM network can also be used alone for a message

transmission (without ISDN).

For application according to VdS, only backup path

transmission from D1 to D1 or D2 to D2 is permissible.

Antenna planning

The antenna selection depends on the measured field

strength. The antenna and the cable must be selected

so that the measured attenuation on the AT 2000 does

not exceed -87 dB.

If the antenna is placed near an automatic fire or

intrusion detector, the distance of the antenna to the

detector must be at least 1 m.

We generally recommend the use of a radiator (rod

antenna for exterior and interior areas). If the reception

level implemented with a radiator is insufficient, beam

antennas (planar or exterior antennas for exterior and

interior areas) should be used.

With the installation of antennas outdoors, the relevant

DIN VDE provisions, especially DIN VDE 0845 part 1 and

VdS 2311 appendix F (protection against lightning)

must be adhered to! The ground connection isolator

and the lightning protection set (optional) are designed

for this.

Make measurements precisely where the antenna will

be mounted. The measurement results must remain

stable for a period of 10 minutes.

Antenna

Gain

Cable attenua-
tion

Comments

Magnet foot

antenna

0 dBi

(Entire system)

2.6 m fixed cable

with FME connec-

tor, female

Rod antenna

3.5 dBi

(Value without ca-

ble)

0.3 dB/m

With 20 m fixed

cable, with FME

connector, fe-

male

Planar antenna

8 dBi

According to ca-

ble type

Type of connec-

tion N-connector

Exterior antenna 10 dBi

According to ca-

ble type

Connection type:

7/16 connector

Antenna cable

Cable type

Cable
attenuation

Cable Ø

Comments

Standard cable

0.3 dB/m

Approx. 5 mm

Low loss cable

Aircom Plus

0.15 dB/m

10.8 mm

SOHA

If necessary, the pre-configured cables must be

shortened in order to avoid unnecessary attenuation.

The Aircom Plus cable must be used if the low-

attenuation standard cable achieves no level better

than -87 dBm.

Applications must strictly adhere to the bending radius

of at least 55 mm.

Product ID
4.998.066.838

Aircom Plus cable (SOHA)

4.998.066.839

Expansion module connector for the

Aircom Plus cable (SOHA)

Fire detection technology

Interface according to VDE 0833 part 2 can be provided

optionally.

Parts Included

Type

Qty.

Component

AT 2000 TSN ISDN 1

AT 2000 installation module with housing,

power supply unit and GSM module

Technical Specifications

Housing version
Current consumption

Standby current

Approx. 125 mA

ISDN transmission

Approx. 127 mA

GSM transmission

Approx. 255 mA

Additional current per activat-

ed relay

Approx. 12 mA

Terminal resistance of the

primary line

10 kilohm ± 1%

Activation time

> 200 ms

Load on switch contacts

Max. output

30 W/60 VA (Ohm resistive load)

Max. voltage

50 V

ambient temperature

-0 °C to +50 °C

Environmental class

II

Protection category

IP 40

Housing

Dimensions (H x W x D)

366 x 258 x 103 mm

Color

Light gray

Weight without/with battery

4.0/8.0 kg

Bosch Security Systems B.V.

www.boschsecurity.com

7

Advertising