Bosch 8-Dec User Manual

Page 337

Advertising
background image

LSN Peripherals | LSN Smoke | 329

-

UEZ 2000 LSN Universal Fire Panel

-

UGM 2020 Universal Security System

-

Plus other fire panels and their receiver modules

with identical connection conditions.

Country-specific standards and guidelines must be

observed during the planning phase.

Installation/configuration notes in accordance with VdS/

VDE/DIBt

The OTC, OC and OT types are planned in accordance

with the guidelines for optical detectors if operated as

optical detectors or combined detectors (see

DIN VDE 0833 Part 2 and VDS 2095).

If occasional disconnection of the optical unit

(scattered light sensor) is required, planning must be

based on the guidelines for heat detectors (see

DIN VDE 0833 Part 2 and VDS 2095):

When planning fire barriers according to DIBt, note that

the T 400 LSN must be configured in line with class A1R.

Parts Included

Detector type Qty.

Components

OTC 410

1

Multisensor Detector Optical/Thermal/Chemical

OC 410

1

Multisensor Detector Optical/Chemical

OT 400 E

1

Multisensor Detector Optical/Thermal

O 400 E

1

Optical Smoke Detector

T 400 E

1

Heat Detector (Thermal Differential/Thermal

Maximum)

OT 400 KKW

1

Multisensor Detector Optical/Thermal *

O 400 KKW

1

Optical Smoke Detector *

T 400 KKW

1

Heat Detector (Thermal Differential/Thermal

Maximum) *

*For use in areas with increased radioactive radiation

Technical Specifications

Electrical

Operating voltage

15 V DC . . . 33 V DC

Current consumption

< 0.7 mA

Alarm output

Per data word by two-wire signal line

Indicator output

Open collector connects 0 V over 1.5 kΩ,

max. 15 mA

Mechanics

Individual display

LED red

Dimensions

Without base

Ø 99.5 x 52 mm

With base

Ø 120 x 63.5 mm

Housing

Material

Plastic, ABS (Novodur)

Color

White, similar to RAL 9010,

matt finish

Weight

Without / with packaging

OTC 410 / OC 410

Approx. 80 g / approx. 125 g

OT 400 / O 400 / T 400 Approx. 75 g / approx. 115 g

Environmental conditions

Protection class as per

EN 60529

IP 30,

IP 32 with damp room seal

Permissible operating temper-

ature

OTC 410

-10 °C . . . +50 °C

OC 410

-10 °C . . . +50 °C

OT 400

-20 °C . . . +50 °C

O 400

-20 °C . . . +65 °C

T 400

-20 °C . . . +50 °C

Permissible relative humidity 95% (non-condensing)
Permissible air speed

20 m/s

Planning

Monitoring area

OTC 410, OC 410,

OT 400, O 400

Max. 120 m

2

(Heed local guidelines!)

T 400

Max. 40 m

2

(Heed local guidelines!)

Maximum installation height

16 m (Heed local guidelines!)

OTC 410, OC 410,

OT 400, O 400

16 m (Heed local guidelines!)

T 400

7.5 m (Heed local guidelines!)

Special features

Response sensitivity

Optical part

< 0.15 dB/m, in line with EN 54 T7

Thermal maximum part > 54 °C / >69 °C

Thermal differential

part

A1R / A2R / BR, as per prEN 54‑5 (pro-

grammable)

Gas sensor

In ppm range

Color code

OTC 410

Yellow loop

OC 410

Blue loop

OT 400

Black loop

O 400

No marking

T 400

Red loop

Ordering Information

Accessories

MS 400 Detector Base

for surface-mounted and flush-mounted cable

feed

MS 400

MSF 400 Detector Base with Damp Room
Seal

for surface-mounted and flush-mounted cable

feed

MSF 400

MSC 420 Additional Base with Damp Room
Seal

for surface-mounted cable feed

MSC 420

MS 420 LSN Detector Base with Spring

for use in Great Britain

MS 420

MPA External Detector Alarm Display
according to DIN 14623

MPA

www.boschsecurity.com

Bosch Security Systems B.V.

6

Advertising