Bosch 8-Dec User Manual

Page 345

Advertising
background image

LSN Peripherals | LSN Smoke | 337

FAP-OC 520(-P)

180 g / 370 g

FAP-O 520(-P)

170 g / 360 g

Trim Ring

30 g / 60 g

Environmental conditions

Permissible operating tempera-

ture

FAP-O 520 (-P)

-20 °C . . . +65 °C

FAP-OC 520 (-P)

-10 °C . . . +50 °C

Permissible relative humidity

95% (non-condensing)

Permissible air speed

20 m/s

Protection class as per

EN 60529

FAP-O 520 (-P)

IP 53

FAP-OC 520 (-P)

IP 33

Planning

Monitoring area

Max. 120 m

2

(Heed local guidelines!)

Maximum installation height

16 m (Heed local guidelines!)

Minimum installation height

Out of arm's reach

Minimum installation height recommend-

ed by BOSCH: 2.70 m

Minimum distance to lamps

0.5 m

For flush ceiling mounting with

FAA-500-BB

Thickness of the false ceil-

ing

Max. 32 mm

Required bored hole

Ø 130 mm (-1 mm ... +5 mm)

Installation depth

110 mm

Note: Above the false ceiling, a free height

of at least 110 mm is required.

Further characteristics

Detection principle

FAP-O 520(-P)

Scattered light measurement

FAP-OC 520(-P)

Combination of scattered light measure-

ment and combustion gas measurement

Response sensitivity

FAP-O 520(-P)

< 0.18 dB/m (EN 54-7)

FAP-OC 520(-P)

Optical section: < 0.36 dB/m (EN 54‑7)

Gas sensor section: in ppm range

Individual display

Two-color LED,

red (alarm), green (test mode)

Ordering Information

FAP‑O 520 Optical Smoke Detector, White

FAP-O 520

FAP‑O 520‑P Optical Smoke Detector,
Transparent with Color Inserts

FAP-O 520-P

FAP‑OC 520 Multisensor Detector Optical/
Chemical, White

FAP-OC 520

FAP‑OC 520‑P Multisensor Detector
Optical/Chemical, Transparent with Color
Inserts

FAP-OC 520-P

Ordering Information

Accessories

FAA‑500‑TR-W Trim Ring, White

for 500 and 520 Series Fire Detectors

FAA-500-TR-W

FAA‑500‑TR‑P Trim Ring, Transparent with
Color Inserts

for 500 and 520 Series Fire Detectors

FAA-500-TR-P

FAA‑500 LSN Base

for installation of the FAP‑520 Fire Detector

FAA-500

FAA‑500‑R LSN Base with Relay

Only used in conjunction with the 5000 Series

Modular Fire Panel.

FAA-500-R

FAA‑500‑GB LSN Base for GB

FAA-500-GB

FAA‑500‑R‑GB LSN Base with Relay for GB

Only used in conjunction with the 5000 Series

Modular Fire Panel.

FAA-500-R-GB

FAA‑500‑BB Ceiling Mount Back Box

for ceiling flush installation in false ceilings

when mounting 500 and 520 Series Bases and

Fire Detectors

FAA-500-BB

FAA‑500‑CB Built-in Housing for Concrete
Ceilings

FAA-500-CB

FAA‑500‑SB Surface Mount Back Box

FAA-500-SB

FAA‑500‑SB-H Surface Mount Back Box
with Damp Room Seal

FAA-500-SB-H

FAA‑500‑SPRING for Concrete/Wooden
Ceilings

(DU = 10 units)

FAA-500-SPRING

www.boschsecurity.com

Bosch Security Systems B.V.

6

Advertising