68 | Accessories for Control Panels and Keypads | Expansion Modules

DX2010 Series Input

Expander

Features

Up to eight sensor input loops
Directly connects to the control panel data bus

The DX2010 Input Expander connects directly to the data
bus of a compatible control panel. Each expander adds
eight input loops. Install up to five expanders in a control
panel's enclosure (three on the interior sidewalls and two
on the back wall of the enclosure).

Certifications and Approvals

Region

Certification

Europe

CE

DX2010: 1999/5/EC, 2006/95/EC,
2004/108/EC; EN 55022:2006 +
A1:2007, Class B; EN 50130-4 w/
A1:1998 + A2:2003;
EN61000-3-2:2006;
EN61000-3-3:1995; EN 60950-1:2001;
TBR21:1998

Belgium

INCERT

DX2010 and DX2012 only

USA

UL

DX2010: AMCX: Central Station Alarm
Units (UL1610, UL1635), AMTB: Control
Panels, SIA False Alarm Reduction, AOTX:
Local Alarm Units (UL464, UL609), APAW:
Police Station Alarm Units (UL365,
UL464), APOU: Proprietary Alarm Units
(UL1076), NBSX: Household Burglar
Alarm System Units (UL1023), UTOU:
Control Units and Accessories - Household
System Type (UL985)

CSFM

DX2010: 7167-1615: 183 and
7167-1615: 223 July 2008

France

AFNOR

NF, A2P Type 2 (122000076-03)

Installation/Configuration Notes

Compatibility Information

Control Panels

Easy Series (ICP‑EZM2‑NA, ICP‑EZM2‑UK,

ICP‑EZM2‑LC), D4412, D6412, DS7220V2, and

DS7240V2

Technical Specifications

Outputs

Outputs:

100 mA, 12 VDC supervised output for acces-

sories

Environmental Considerations

Operating Temperature:

0°C to +50°C (+32°F to +122°F)

Relative Humidity:

5% to 85% at +30°C (+86°F), non‑condensing

Loop

Inputs:

Up to eight inputs

Input contacts may be normally‑open (NO) or

normally‑closed (NC) with appropriate end-of-

line resistor(s) for supervision.

Resistance:

60Ω maximum

Terminal Wire Size:

1.8 mm (14 AWG) to 0.8 mm (22 AWG)

Power Requirements

Current (Maximum):

35 mA standby

35 mA maximum with connected accessories

Voltage (Operating):

8 VDC to 14 VDC

Ordering Information

DX2010 Input Expander

Provides hard-wired expansion for an addi-

tional eight input points. Includes the DX2010

board.

DX2010

DX2011 Package

Includes a DX2010 Input Expander with a

D203 Metal Enclosure.

DX2011

DX2012 Package

Includes a DX2010 Input Expander with an

AE20 Plastic Enclosure.

DX2012

Accessories

AE20 Universal Plastic Enclosure

Mounts to a single gang/double gang box, a

9 cm (3.5 in.) octagonal box, or a 10 cm (4 in.)

square box. The dimensions are 12 cm x 16 cm

x 4 cm (4.7 in. x 6.2 in. x 1.5 in.). Accommo-

dates wall tamper switches on the modules.