298 | Detectors and Accessories | Accessories

PEH‑2 Heater

Features

Automatic temperature control maintains a constant

temperature

Made of durable ceramic to withstand weathering
Horizontally adjustable radiator coordinates with the

angle of photoelectric detector optical modules

The PEH-2 Heater is a heating device that prevents frost
accumulation on photoelectric beam detector covers,
promoting stable performance.

Installation/Configuration Notes

Compatibility Information

Photoelectric Beam Detectors

DS484Q, DS486Q, DS453Q, and
DS455Q

Parts Included

Quantity

Component

2

Heaters (heating element, radiator, terminal)

4

Heater mounting screws

4

Terminal mounting screws

2

Stoppers

1

Installation Guide

Technical Specifications

Weight

Total Weight:

15 g (0.03 lb)

Environmental Considerations

Operating Temperature:

-25°C to +60°C (-13°F to +140°F)

Relative Humidity (RH):

Up to 95%

Surface Temperature:

+55°C (131°F)

Power Requirements

Power Supply Voltage:

20 VDC to 28 VDC non-polarized

Current Draw:

350 mA maximum when power is ap-

plied 110 mA during operation (for

each heater)

Backup Power Requirements:

4 hours (440 mAh) minimum required

for UL Certificated Installations

Ordering Information

PEH‑2 Heater

Reduces the effects of frost, intense fog, cold,

and damp conditions on photoelectric beam

detectors. Shipped in packages of four (two for

transmitter and two for receiver).

PEH2

Bosch Security Systems B.V.

www.boschsecurity.com

5