Detectors and Accessories | Smoke | 239

F220‑PTHC

1

Photoelectric Smoke Detector with +135°F

(+57°C) Heat Sensor and Carbon Monoxide Sensor
Enhancement

1

F220‑135 Electronic Rate‑of‑Rise, Fixed Temperature

+135°F (+57°C) Heat Detector

F220‑135F Electronic Fixed Temperature +135°F

(+57°C) Heat Detector

F220‑190F Electronic Fixed Temperature +190°F

(+88°C) Heat Detector

1

The F220‑PTHC detects carbon monoxide (CO) as a

component of a fire. It is not a CO detector and cannot
activate an alarm in the presence of CO only.
Mounting Considerations
Depending on local regulations, surface mount the bases
using anchors, mollies, or wing nuts, or mount directly on
four‑inch square or octagonal electrical boxes or
single‑gang switch boxes.

Note

The electrical box must be large enough to
accommodate the number and size of
conductors specified by the National Electrical
Code or any local authorities having
jurisdiction (AHJ).

Wiring Considerations
In a four-wire system, the maximum loop length and number
of bases that can be placed on a loop depend on the voltage
drop on the power circuit. Use standard voltage drop
calculations to ensure that the last detector on the loop has
at least 16 V when all sounders and relays are powered.

Parts Included

Quant.

Component

1

Detector base

1

Literature pack

Technical Specifications

Environmental Considerations

Relative Humidity:

0 to 95%, non‑condensing; 15% to 95%,

non‑condensing when used with CO sensor

model

Temperature (operating):

+32°F to +100°F (0°C to +38°C)

Mechanical Properties

Color:

Off-white

Dimensions (diameter x thick-

ness)

6 in. x 0.9 in. (15.2 cm x 2.3 cm)

Material:

Fire‑resistant plastic

Outputs

Relay Type:

Normally‑open (NO) Form A

Relay Rating:

0.5 A at 120 VDC or 120 VAC

Sounder Output:

>85 dB at 10 ft (3 m)

Power Requirements

Voltage Range:

16.0 VDC to 30 VDC

Alarm Current
6-wire mode (4-wire base + two sounder power wires)
Relay:

The relay draws 15 mA in alarm.

Steady Sounder:

24 VDC: 30 mA

30 VDC: 35 mA

4-wire mode
With Steady Sounder

and Relay:

24 VDC: 45 mA

30 VDC: 50 mA

Standby Current (base only):

30 VDC: 10 mA maximum

Ordering Information

F220‑B6RS 24 VDC Four‑wire Detector
Base with Sounder

Four-wire detector base with sounder for use

with the F220 Series Photoelectric Smoke and

Heat Detectors.

F220-B6RS

www.boschsecurity.com