40 | Control Panels, Control Centers, and Keypads | 7000 Line

PO 2: can be used with Alarm + as a supervised siren driver.
Connect an approved 4 Ω or 8 Ω speaker. Alternatively, PO 2
can sink up to 500 mA, 12 VDC.
PO 3 and PO 4: can be configured for Alarm Output. These
outputs can sink 500 mA, 12 VDC each.

Certifications and Approvals

Region

Certification

Europe

CE

1999/5/EC, 2006/95/EC, 2004/108/
EC; EN 55022:2006 + A1:2007, Class B;
EN 50130-4 w/A1:1998 + A2:2003;
EN61000-3-2:2006;
EN61000-3-3:1995; EN 60950-1:2001;
TBR21:1998

Russia

GOST

GOST 12997-84, GOST R MEK
60065-2002, GOST R 50009-2000,
GOST R 51317.3.2-99, GOST R
51317.3.3-99

France

AFNOR

NF, A2P (122077-00)

China

CCC

2005031902000137

Sweden

INTYG

Nr05-303

Brazil

ANATEL

1240-05-1855

The DS7220V2 Control Panel is designed to comply with the following cer-

tifications, approvals, and standards.
EN50131-1 grade 2

Installation/Configuration Notes

Compatibility Information

Batteries

D126 12 V, 7 Ah Standby Battery
D1218 12 V, 18 Ah Standby Battery
D1240 12 V, 4 Ah Standby Battery

Keypads

DS7445i LED Keypad
DS7445V2 LED Keypad
DS7446KP LCD Keypad
DS7447E LCD Keypad
DS7447V2 LCD Keypad

Fire Detectors

D132A Smoke Detector Reversing Relay
DS250 Photoelectric Smoke Detector
DS250TH Photoelectric Smoke Detector with

heat-sensing thermistor
DS284 Photoelectric Smoke Detector
DS284TH Photoelectric Smoke Detector with

heat-sensing thermistor
DS284THS Photoelectric Smoke Detector with heat-

sensing thermistor and sounder

Wireless Prod-

ucts

RF280ETHS Wireless Photoelectric Smoke Detector

with heat-sensing thermistor and sounder
RF835E Wireless TriTech

®

Detector

RF940E Wireless PIR Detector
RF1100E RF Glass Break Detector

Batteries

D126 12 V, 7 Ah Standby Battery
RF3227E RF Receiver
RF3332E Two-button Keyfob
RF3334E Four-button Keyfob
RF3401E RF Transmitter
RF3405E RF Inertia Transmitter
RF3501E RF Panic Pendant
RF3503E RF Panic Button

Modules

DACM Door Access Control Module
DX2010 Eight-input Expander
DX2011 Eight-input Expander - D203 Metal Enclosure
DX2012 Eight-input Expander - AE20 Plastic Enclosure
DX3010 Octo-output Expander
DX3020 X-10 Control Module
DX4010 RS-232 Serial Interface Module
DX4010i RS-232 Serial Interface Module
DX4020 Network Interface Module
rvm4c Remote Video Module

Wiring Considerations

Up to 305 m (1,000 ft) allowed between panel/external

power supply and keypad or DACM when using 0.8 mm

wire.

Up to 610 m (2,000 ft) allowed between panel/external

power supply and keypad or DACM when using 1.2 mm

wire.

No more than two keypads/DACMs (0.8 mm) or three

keypads/DACMs (1.2 mm) are recommended on any

305 m (1,000 ft) run when powered from the panel.

Parts Included

Each standard system includes:

Quantity Component
1

DS7220V2 control board

1

Universal enclosure

1

Transformer (18 VAC, 50 VA)

1

Hardware/resistor pack

Technical Specifications

Data Bus

Data Bus:

12 VDC nominal

Enclosure

Material:

1.0 mm, cold-rolled steel

Dimensions:

36.8 cm x 31.8 cm x 7.6 cm

(14.5 in. x 12.5 in. x 3 in.)

Environmental Considerations

Relative Humidity:

5% to 85% at +30°C (+86°F) non-condens-

ing

Temperature (Operating):

0°C to +49°C (+32°F to +120°F)

Bosch Security Systems B.V.

www.boschsecurity.com

1