EMK 36 AT LSN Surface-

Mount Magnetic Contact

Features

LSN surface-mount magnetic contact
VdS class B
Parallel mounting
LSN perimeter protection

Magnetic contacts are used for tear-off surveillance of
doors and windows.

Certifications and Approvals

Region

Certification

Europe

CE

EMK 36 AT LSN

Germany

VdS

G 101504, B EMK 36 AT LSN

Installation/Configuration Notes

Installation notes

EMK 36 AT LSN installation is parallel.

For installation on ferromagnetic materials, the

distance plates must be used.

The contacts are generally installed in the door or

window frames with the magnet in the window or the

door. If the door or window is opened less than 1 cm,

the magnetic contact should not be able to detect this.

An opening of more than 3 cm must be detected.

1

Contact

2

Magnet

Distances diagram (parallel mounting)

1

Extraction

2

Proximity switch part

Connecting LSN contacts

Every LSN contact is a physical LSN element (1 out of

127 possible per loop).

The length of LSN contact connection cables must be

included when planning the total line length of the LSN

loop, as LSN technology is incorporated in these

detectors.

Passive coupling elements for joining the connection

cables to the installation cable must be placed as close

as possible to the LSN contacts. The 1 m connection

cable with 2 m LSN cable length is included in the

calculation of the LSN cable length (LSN is carried into

the contacts and back out again).

Connector boxes (optional) are classified as installation

material.

Testing LSN contacts

Reed switch and microswitch functions can be checked

before installation by a high-Ohm multimeter or

continuity checker (for diode paths).

The resistance values are approximate values; a large

change in resistance is significant here.

1

Detector

2

High-Ohm multimeter

Contact open: approx. 3 MOhm

Contact closed: approx. 1 megaohm

Note

Only the intrusion contact can be checked in
this way. The tamper switch of the Class C

www.boschsecurity.com