Bosch 8-Dec User Manual

Page 243

Advertising
background image

Detectors and Accessories | Smoke | 235

Two-wire: Bosch Security Systems, Inc. makes no claim
written, oral, or implied that the F220 Heat Detectors work
with any two-wire control panels except those specified in
the Control Panel Compatibility chart in the Technical
Service Note (P/N: 4998148185).
Four-wire: compatible with all UL Listed four-wire control
panels. Refer to the control panel's installation instructions
for proper end-of-line (EOL) resistor selection.
Mounting the Bases

Note

Consult NFPA 72 for proper detector
placement.

Depending on local regulations, the bases can be surface
mounted directly on four-inch square or octagonal electrical
boxes and single-gang switch boxes.

Note

The volume of any electrical box used should
be adequate to accommodate the number and
size of conductors as specified by the National
Electrical Code or any local authorities having
jurisdiction (AHJ).

End-of-Line Power Supervision
Loop supervision requires one D275 or F220-B6E per loop
when using F220-B6R/B6C bases and is accomplished by
the control panel.
Wiring the Bases
Refer to the F220 Series Detectors with F220-B6/C/E/R
Bases Installation Instructions (P/N: 4998138694), the
F220 Series Detectors with F220-B6RS Bases Installation
Instructions (P/N: F01U029847), or the F220-B6PS/M
Installation Instructions (P/N: 4998149982) for detailed
wiring instructions.

Technical Specifications

Environmental Considerations

Relative Humidity:

0% to 95% non-condensing

Temperature

(normal operating):

+32°F to +100°F (0°C to +38°C)

Note: The normal environment where these detectors are installed should

be within the specified normal operating temperature limits.

Mechanical Properties

Color:

White

Dimensions (diameter x H): 6.75 in. x 2.25 in. (17.1 cm x 6.4 cm)

Power Requirements

Current (alarm):

(detector head only)

20 mA minimum at 8.5 VDC;

35 mA maximum at 32 VDC

Current (start-up):

0.12 mA maximum at 35 VDC

Maximum RMS Ripple:

25% of DC input

Power-up Time:

22 sec maximum

Voltage (standby)
F220‑B6:

8.5 VDC to 32.0 VDC

F220‑B6C/‑B6R/‑B6E:

10.0 VDC to 30.0 VDC

F220‑B6RS:

16.0 VDC to 30.0 VDC

F220‑B6PM:

18.9 VDC to 28.0 VDC

F220‑B6PS:

With D299: 18.9 VDC to 28.0 VDC

Without D299: 9.6 VDC to 28.0 VDC

Ordering Information

F220‑135 Electronic Rate‑of‑Rise/Fixed
Temperature (+135°F [+57°C]) Heat
Detector

Rate‑of‑rise/fixed temperature heat detector

head only; requires base.

F220-135

F220‑135F Electronic Fixed Temperature
(+135°F [+57°C]) Heat Detector

Fixed temperature heat detector head only;

requires base.

F220-135F

F220‑190F Electronic Fixed Temperature
(+190°F [+88°C]) Heat Detector

Fixed temperature heat detector head only;

requires base.

F220-190F

Accessories

F220‑B6 12/24 VDC Two‑wire Base

Standard base for two‑wire (12 VDC or 24 VDC

system) applications.

F220-B6

F220‑B6R Standard 12/24 VDC Four‑wire
Base

Standard base for four‑wire (12 VDC or

24 VDC) detector systems.

F220-B6R

F220‑B6RS 24 VDC Four‑wire Detector
Base with Sounder

Four-wire detector base with sounder for use

with the F220 Series Photoelectric Smoke and

Heat Detectors.

F220-B6RS

F220‑B6C 12/24 VDC Four‑wire Base with
Auxiliary Form C Relay

Four‑wire base with a normally‑open (NO)

alarm loop relay and a set of auxiliary contacts

(Form C).

F220-B6C

F220‑B6E 12/24 VDC Four‑wire Power
Supervision Base with End‑of‑line Power
Monitoring Relay

Four‑wire base with a normally‑open (NO)

alarm relay and an EOL power supervision re-

lay.

F220-B6E

www.boschsecurity.com

Bosch Security Systems B.V.

5

Advertising