Conettix d6680 ethernet network adapter, Conettix ip – Bosch 8-Dec User Manual

Page 417

Advertising
background image

Conettix - Information Transport Solutions | Conettix IP | 409

Conettix D6680 Ethernet

Network Adapter

Features

Two channel adapter
Network interface
Serial interface

The Conettix D6680 Ethernet Network Adapter is a two-
channel network adapter. The D6680 connects the Conettix
D6600 Communications Receiver/Gateway RS-232 Data
Port to an Ethernet LAN/WAN. One adapter is required for
each D6600 serial port with a direct connection to a data
network (LAN/WAN).

Certifications and Approvals

Install the Conettix D6600 Communications Receiver/
Gateway in accordance with NFPA 70, NFPA 72 and the local
Authority Having Jurisdiction (AHJ). The Conettix D6680
Ethernet Network Adapter is suitable for Central Station
Protective Signaling when it is installed and used in
compliance with NFPA 72 and ANSI/NFPA 70. Installation
limits for Digital Alarm Communicator Receivers (DACR) are
under the jurisdiction of the user’s local authority.
For UL Listed Fire Installations, equipment between
Ethernet Interface Modules and the D6680 is required to be
UL Listed Information Technology Equipment.

Region

Certification

USA

UL

AMCX: Central Station Alarm Units
(UL1610, UL1635), UOXX: Control Unit
Accessories, System (UL864, 9th edition)

FM
CSFM

7300-1615: 179 July 2008

Installation/Configuration Notes

Compatibility Information

Receivers:

Conettix D6600 Communications Receiver/Gate-

way

Location and Enclosures
The D6680 must be installed in the same room as the D6600
and within 15.2 m (50 ft) of the D6600. Required for UL
Central Station Protective Signaling, the D6680 must be
mounted in a separate enclosure such as the AE1 (gray) or
the AE2 (red).

Parts Included

Quantity

Component

1

Serial cable

Technical Specifications

Electrical

Power Requirements:

9 VDC to 30 VDC, or 9 VAC to 25 VAC

External adapter included.

Power Consumption:

3 W

AC Current Required:

UPS Standby Current:35 mA

Power Input:

AC nominal operating range 120 VAC or

240 VAC

AC maximum operating range 100 VAC to

240 VAC ~ 50 Hz /60 Hz

0.2 A maximum

Standby Power:

An Uninterrupted Power Supply is required for

use with the D6680, when used for UL FIRE

Protective

Signaling Systems. A 60 hour minimum UPS

standby power supply is required for UL Cer-

tification.

Mechanical

Unit Dimensions:

16.5 cm x 11.3 cm x 36 mm (6.5 in. x 4.46 in.

x 1.39 in.)

Enclosure Dimensions:

31.8 cm x 36.8 cm x 76 mm (12.5 in. x 14.5

in. x 3 in.)

The enclosure is manufactured from 1.0 mm

(20 Gauge), cold-rolled steel. A keyed lock is

included.

Weight:

0.48 kg (1.1 lb)

Protocols Supported:

ARP, UDP, TCP, Telnet, ICMP, SNMP, DHCP,

TFTP, HTTP, BootP and ECHO

Serial Connectors:

DB25: RS-232/RS-322/RS-485 serial port

with DCE configuration

DB9: RS232 serial port with DTE

configuration

Network Connectors:

10BASE-T or 10BASE-FL

LAN/WAN: RJ-45 Modular Jack (Ethernet)

Ethernet Cable:

Category 3 or better unshielded twisted pair.

Maximum length 100 m (328 ft).

RS-232 Cable:

Maximum length 15 m (50 ft).

www.boschsecurity.com

Bosch Security Systems B.V.

7