F220 photoelectric smoke detectors, Smoke – Bosch 8-Dec User Manual

Page 239

Advertising
background image

Detectors and Accessories | Smoke | 231

F220 Photoelectric Smoke

Detectors

Features

Two-wire or four-wire bases
30 ft (9 m) maximum spacing between detectors
Optional CO-sensor, heat-sensor enhanced detection

chamber

Clean chamber without removal or disassembly
CleanMe

®

signaling capability

Sensitivity readout on detector
Detector chamber compensates for dust build-up
Tamper protection
Dual-color LED

The F220 Photoelectric Smoke Detectors are UL Listed,
open-area photoelectric smoke detectors. Use them with
commercial fire protective signaling systems and household
fire warning systems (see NFPA 72, the National Fire Alarm
Code). These smoke detectors scatter light using a pulsed
infrared source operating with a gated, high-speed,
photodiode infrared sensor. The symmetry of the optical
chamber allows 360° uniform smoke entry, but minimizes
external light entry. The detectors use low current
electronic circuitry, so they can connect to 12 VDC nominal
or 24 VDC nominal power source circuits.

Functions

Compatible Bases
Configure the detectors into two-wire or four-wire versions
by selecting the appropriate mounting base. These
detectors are compatible with any of the F220‑B6 bases:

F220-B6 12/24 VDC Two‑wire Mounting Base

F220-B6R Standard 12/24 VDC Four‑wire Mounting

Base

F220-B6RS 24 VDC Four‑wire Mounting Base with

Sounder

F220-B6C 12/24 VDC Four‑wire Mounting Base with

Auxiliary Relay

F220-B6E 12/24 VDC Four‑wire Power Supervision

Mounting Base

F220-B6PM 24 VDC Four‑wire Addressable Master Base

F220-B6PS 12/24 VDC Four‑wire Addressable Base

Monitoring the Detection Chamber
These detectors have several features that work together to
maximize the performance of the optical chamber:

Compensation: The detector monitors the chamber for

the effects of dust build-up within the chamber and

automatically compensates for these effects. If the

chamber becomes contaminated beyond its ability to

compensate, the green LED flashes every 4 sec to

indicate trouble.

Chamber Check® Self-diagnostics: The detector

automatically indicates visually if the calibration is out

of the factory-listed range. This meets NFPA guidelines

for sensitivity testing, because you can visually inspect

the detector and check the flash rate of the LED. If the

calibration is out of range, the green LED on the

detector flashes once every 4 sec. This indicates that

the detector must be cleaned following the instructions

provided with the detector.

CleanMe Mode: Indicates if the calibration is out of the

factory-listed range by sending a trouble signal to the

CleanMe-compatible control panel, if so programmed.

Chambermaid™: The detector has a unique cleaning

mechanism. Use the valve on the back of the detector

to insert the nozzle of a can of clean, dry compressed

air. Clean the chamber with a short (1 to 2 sec) blast of

air.

Heat and Carbon Monoxide Enhancements
The detectors are available with an optional fixed-
temperature heat sensor, a carbon monoxide (CO) sensor,
or a combination of heat and CO sensors. These optional
sensors enhance the operation of the smoke detector by
reducing false alarms.

Carbon Monoxide: Without the presence of CO, a

normal byproduct of combustion, the detection

chamber is half as sensitive to smoke as a standard

commercial photoelectric smoke chamber. This

reduces false alarms. When the sensor detects CO, the

detection chamber's sensitivity to smoke increases so

it equals or exceeds that of a standard commercial

photoelectric smoke chamber.

Note

The F220-PTHC detects carbon monoxide (CO)
as a component of a fire. It is not a CO detector
and cannot activate an alarm in the presence
of CO only.

Heat: When the heat sensor detects a temperature rise,

the photoelectric chamber becomes more smoke

sensitive. The heat sensor initiates an alarm if the

ambient temperature exceeds +135°F (+57°C).

www.boschsecurity.com

Bosch Security Systems B.V.

5

Advertising