80 | Accessories for Control Panels and Keypads | Expansion Modules

DS7465i Input‑Output

Module

Features

Supervises one power-limited input zone
Provides one output relay
Can be used in UL Listed fire and security applications
DIP switch programmable

The DS7465i Input-Output Module works with compatible
multiplex systems and uses two multiplex zone addresses.
It supplies a DIP switch programmable Form C relay (output
zone) that activates on several different system events. The
DS7465i Module provides an input zone for monitoring
conventional normally-open (NO) or normally-closed (NC)
contacts. The module reports the contact status as a
multiplex address to the control panel. Use up to sixty
DS7465i Modules with compatible control panels or
multiplex expansion modules.

Functions

Supervised Input Zone
The power-limited input zone is designed to monitor NO or
NC dry contacts. It is supervised using 47 kΩ end-of-line
(EOL) resistors.
Output Relay
Use the output relay only on power-limited circuits. The
relay contacts are rated 1 A at 30 VDC for resistive loads.
Do not use the output relay with inductive or capacitive
loads.

Certifications and Approvals

Region

Certification

Europe

CE

89/336/EEC, EN55022: 1998,
EN50130-4: 1995, EN60950: 2000,
EN61000-3-2, EN61000-3-3,
EN61000-4-2, EN61000-4-3,
EN61000-4-4, EN61000-4-5,
EN61000-4-6, EN61000-4-11

USA

UL

NBSX: Household Burglar Alarm System
Units (UL1023), UOXX: Control Unit
Accessories, System (UL864, 9th edition),
UTOU: Control Units and Accessories -
Household System Type (UL985)

CSFM

7165-1615: 113, 7165-1615: 119,
7170-1615: 144, and 7170-1615:
145 July 2008

Installation/Configuration Notes

Compatibility Information

Control Panels

D9412GV2, D7412GV2, and D7212GV2 Control

Panel
D9412G, D7412G, and D7212G Control Panel
D9124 Fire Alarm Control Panel
DS7400Xi Control Panel

Multiplex Modules

D8125MUX Multiplex Bus Interface
DS7430 Multiplex Expansion Module
DS7436 Multiplex Expansion Module

The DS7465i Series Modules require a multiplex expansion
module to connect to the control panels.

Fire Applications
For UL Listed fire installations, normally-open (NO)
contacts must be used. For fire installations, order
Multiplex-zone Fire EOL resistors (P/N: 28010) in the
quantity needed.
Wiring

Maximum Impedance: 4.05 Ω at +20°C (+68°F) nominal
Distance (approximate)

Size

76 m

0.65 mm

193 m

1.02 mm

250 ft

22 AWG

600 ft

18 AWG

Refer to the multiplex expansion module’s reference guide for
multiplex wiring requirements.

The recommended wiring to the control panel is quad (four-
wire) cable. Do not use shielded or twisted pair cable.

Note

If used in fire applications, 18 AWG wire is
required.