372 | LSN Peripherals | LSN Expansion Modules

Connecting conventional detectors

1

Control panel

2

LSN element

3

1-4 DC primary lines

4

Loop

Detection and control via two wires
In local security networks, detection and control functions
are performed via the LSN line. This means additional
primary lines in the control panel are not required for
control procedures.

1

Control panel

2

LSN element

3

Control

4

Loop

5

Stub

Optional KR 100 LSN relay module for LSN expanders
The KR 100 LSN relay module for LSN expanders is intended
for use in the NNK 110 LSN and NVK 100 LSN.
The KR 100 LSN is installed if the high power requirement
of the connected control elements results in these
becoming impossible to actuate directly by the LSN
expanders, or in order to enable zero-potential switching.
Up to four KR 100 LSNs can be installed per NNK 110 LSN
or NVK 100 LSN. One solder distributor is supplied per two
KR 100 LSNs.

Parts Included

Type

Qty.

Component

NNK 110 LSN

1

Emergency call coupler

Technical Specifications

Operating voltage

LSN part

+12 V to +33 V

Other expansion module func-

tions

+9 V to +30 V

Current consumption

2.2 mA for LSN part and 7 mA for the

other expansion module functions

Control output 1 (terminal 14)

Open collector, 0 V when active

Switching voltage

Max. 30 V

Switching current

Max. 20 mA

Control output 2 (terminal 13)

Open collector, 0 V when active

Switching voltage

Max. 30 V

Switching current

Max. 20 mA

Control output 2 (terminal 12)

Open collector, 0 V when inactive

Switching voltage

Max. 30 V

Switching current

Max. 10 mA

Control output 3

(connection 15, 16)

Open collector, 12 V when active

Switching voltage

< 1.5 V

Switching current

Max. 100 mA

Output voltage

+ 12.65 V

Output current

Max. 100 mA

(The total of all V

0

outputs and control

output)

Connection options

4 DC primary lines

1 - 4 primary lines (PL)

Terminal resistance

RE = 12k1 Ohm 1%

Alarm criteria

± 40% of terminal resistance

Line resistance

Max. 100 Ohm

Response time

< 200 ms

Closure monitoring

Max. 100 Ohm

Ambient temperature

-5 °C to +45 °C

Housing base/cover

Plastic

Color

RAL 9002 grayish white

Weight

Approx. 400 g

Dimensions (H x W x D)

215 x 160 x 35.5 mm

Protection category

IP 30

Environmental class

II (VdS 2110)

KR 100 optional

Reel

Response voltage

> 7 V

Fall-off voltage

< 1 V

Reel voltage

Max. 14.3 V

Contacts
Principle

2 change-over contacts zero poten-

tial

Starting current

Max. 5 A

Permanent current

Max. 2 A

Switch-off current

Max. 1 A

Switching voltage

Max. 60 V

Switching performance

Max. 30 W

Bosch Security Systems B.V.

www.boschsecurity.com