Ds7457i series single zone input modules – Bosch 8-Dec User Manual

Page 83

Advertising
background image

Accessories for Control Panels and Keypads | Expansion Modules | 75

DS7457i Series Single Zone

Input Modules

Features

Power-limited and supervised input zones
Compact enough to fit within most back boxes and

enclosures

Address settings through DIP switches

The DS7457i Series Single Zone Input Modules includes the
DS7457i and the DS7457iF. Each model has a supervised
input zone for connecting normally-open (NO) or normally-
closed (NC) contacts. The DS7457i Series supervises the
contacts using 47 kΩ end-of-line(EOL) resistors. Each
model operates with compatible multiplex expansion
modules and occupies one multiplex zone address on the
system. The DS7457i is designed for intrusion applications
while the DS7457iF is designed for fire applications.

Certifications and Approvals

Region

Certification

Europe

CE

DS7457iF: 89/336/EEC, EN55022:
1998, EN50130-4: 1995, EN60950:
2000, EN61000-3-2, EN61000-3-3,
EN61000-4-2, EN61000-4-3,
EN61000-4-4, EN61000-4-5,
EN61000-4-6, EN61000-4-11

USA

UL

Both models: AMCX: Central Station Alarm
Units (UL1610, UL1635), AOTX: Local
Alarm Units (UL464, UL609), APAW:
Police Station Alarm Units (UL365,
UL464)
DS7457iF only: NBSX: Household Burglar
Alarm System Units (UL1023), UOXX:
Control Unit Accessories, System (UL864,
9th edition), UTOU: Control Units and
Accessories - Household System Type
(UL985)

CSFM

DS7457iF only: 7165-1615: 113,
7165-1615: 199, 7170-1615: 144, and
7170-1615: 145 July 2008

Installation/Configuration Notes

Compatibility Information

Control Panels

D9412GV2, D7412GV2, and D7212GV2 Con-
trol Panel
D9412G , D7412G, and D7212G Control Panels
D9412, D7412, and D7212 Control Panels
DS7400Xi Control Panel

Multiplex Modules

D8125MUX Multiplex Bus Interface
DS7430 Multiplex Expansion Module
DS7436 Multiplex Expansion Module

The DS7457i Series Modules require a multiplex expansion
module to connect to the control panels.

Wiring Considerations

Maximum Impedance: 4.05 Ω at +20°C (+68°F) nominal
Distance (approximate)

Size

76 m

0.65 mm

193 m

1.02 mm

250 ft

22 AWG

600 ft

18 AWG

Refer to the intended control panel’s installation guide for
multiplex wiring requirements.

The recommended wiring to the control panel is quad (four-
wire) cable. Do not use shielded or twisted pair cable.

Note

If used in fire applications, 18 AWG wire is
required.

www.boschsecurity.com

Bosch Security Systems B.V.

2

Advertising