background image

LSN Peripherals | LSN Smoke | 341

Region

Certification

Hungary

TMT

TMT-19/2006 FAP-OT 420, FAP-OT 420
KKW, FAP-OTC 420
TMT-17/2006 FAP-O 420, FAP-O 420
KKW
TMT-18/2006 FAH-T 420, FAH-T 420
KKW

Russia

GOST

POCC DE.C313B06300

Detector type

EN54-5:2000/

A1:2002

EN54-7:2000/

A1:2002/

A2:2006

EN54-17:2005

FAP-OTC 420

FAP-OT 420

FAP-O 420

FAH-T 420

FAP-O 420 KKW

FAH-T 420 KKW

Installation/Configuration Notes

For connection to the Modular Fire Panel FPA‑5000 with

the improved LSN system parameters

in "Classic Mode" can be connected to the LSN fire

panels BZ 500 LSN, UEZ 2000 LSN, UGM 2020 and to

other panels or their receiver modules with identical

connection conditions, although with the previous LSN

system parameters

During planning works, it is essential to adhere to

national standards and guidelines.

Installation/configuration notes in accordance with VdS/

VDE

The FAP‑OTC 420, and FAP‑OT 420 types are planned in

accordance with the guidelines for optical detectors if

operated as optical detectors or as combined optical/

thermal detectors (see DIN VDE 0833 Part 2 and

VDS 2095)

If occasional disconnection of the optical unit

(scattered light sensor) is required, planning must be

based on the guidelines for heat detectors (see

DIN VDE 0833 Part 2 and VDS 2095)

When planning fire barriers according to DIBt, note that

the FAH‑T 420 (KKW)must be configured in accordance

with class A1R.

Parts Included

Detector type

Qty.

Components

FAP-OTC 420

1

Multisensor Detector Optical/Thermal/

Chemical

FAP-OT 420

1

Multisensor Detector Optical/Thermal

FAP-O 420

1

Optical Smoke Detector

FAH-T 420

1

Heat Detector (Thermal Differential/Ther-

mal Maximum)

FAP-O 420 KKW

1

Optical Smoke Detector *

FAH-T 420 KKW

1

Heat Detector (Thermal Differential/Ther-

mal Maximum) *

* For use in areas with increased radioactive radiation

Technical Specifications

Electrical

Operating voltage

15 V DC . . 33 V DC

Current consumption

< 0.51 mA

Alarm output

Per data word by two-wire signal line

Indicator output

Open collector connects 0 V over

1.5 kΩ through, max. 15 mA

Mechanics

Dimensions

Without base

Ø 99.5 x 52 mm

With base

Ø 120 x 63.5 mm

Housing

Material

Plastic, ABS (Novodur)

Color

White, similar to RAL 9010,

matt finish

Weight

Without / With packaging

FAP-OTC 420

Approx. 80 g / approx. 125 g

FAP-OT 420, FAP-

O 420 (KKW) and

FAH‑T 420 (KKW)

Approx. 75 g / approx. 115 g

Environmental conditions

Permissible operating tempera-

ture

FAP-OTC 420

-10 °C . . . +50 °C

FAP-OT 420

-20 °C . . . +50 °C

FAP-O 420 (KKW)

-20 °C . . . +65 °C

FAH-T 420 (KKW)

-20 °C . . . +50 °C

Permissible relative humidity

95% (non-condensing)

Permissible air speed

20 m/s.

Protection class as per EN 60529 IP 40,

IP 43 detector base with damp room seal

www.boschsecurity.com

Bosch Security Systems B.V.

6

Advertising