Features

7 parallel inputs, 2 outputs (12 in/12 out optional)
Programmable with PC software (WPAT)
Supports ISDN PTP and PMP
Transmission via ISDN B and D-channel
Monitoring of layer 1 (ISDN constant monitoring)
Tamper and blockade release (ISDN)

The AT 2000 ISDN auto dialer and communicator handles
the transmission of danger alarms, technical alarms/
statuses via the ISDN telephone network.

Functions

Network ac-
cess

Transmission
procedure

Transmission
protocol

receiver

ISDN network

(B-channel)

X.75 with

64 kBit/sec

VdS 2465

ISDN monitoring sta-

tion

Analog

10 baud

Telim

Analog monitoring

station

Data transmis-

sion to TAP/UCP

server

Euromessage

message

SMS plain text

Euromessage receiv-

er, cell phone

(D1/D2)

ISDN network

(D-channel)

X.31 with trans-

fer to X.25

VdS 2465

X.25-/X.31

monitoring station

The signaling occurs on the B-channel (X.75 connection)
and D-channel (X.31 connection).
The AT 2000 ISDN permits connection to multi-device and
equipment connections (PMP/PTP) and is connected in
front of telecommunications equipment and using a
Telekom junction box to the telephone line.

The AT 2000 ISDN can be activated via the serial S1
interface (optional) or the parallel S1 interface with 7 input
line inputs.
The outputs (relay) can be controlled depending on the
message line status (locally) and via remote control
according to VdS 2465 by reception and transmission
equipment.
In the event of tampering or damage to the relaying ISDN
line, the AT 2000 can send a message (tamper release).
The absolute operating procedure on the telephone line is
enabled by the blockade release.
Monitoring of the auto dialer and the telephone network
occurs through a routine call.
The AT 2000 has a tamper contact.
Audio and visual display.
Power monitoring: network, battery, undervoltage
The event storage for up to 512 events can be read out using
a PC.

Certifications and Approvals

Region

Certification

Europe

CE

AT 2000 ISDN

Germany

VdS

G 198802 AT 2000 ISDN

Installation/Configuration Notes

ISDN connection

The AT 2000 ISDN is suitable for connection to basic

access – with the international protocol DSS1.

Primary multiplex connection S2M is not possible.

The AT 2000 ISDN communicator for danger alarms

must be connected to the S

0

bus as the first device.

With this connection, it is possible for the AT 2000 ISDN

to send a message even in the event of tampering or

damage to the bus wiring.

ISDN PTP

The "constant monitoring" layer 1 feature is present by

default for system access.

The max. cable length from network termination NT via

the UAE 8/8 box to the TK system or to the end unit is

1000 m.

ISDN PMP

The "constant monitoring" layer 1 feature is also

required with a multi-system connection.

The max. cable length between network termination

and TK system or end unit is 150 m.

ISDN X.31 transmission

Datex-P ISDN ACCESS 100 (X.31) "Access 100" service

packet for VdS 2465 (D-channel) enables the

configuration of a virtual dedicated line for tamper-

proof transmission. Additional D-channel services can

be used with this application after the AT 2000.

ACCESS ≥ 100 must be applied per MSN.