Detectors and Accessories | Motion PIR | 143

Installation/Configuration Notes

Coverage Patterns

Top View Broad: 11 m x 11 m (35 ft x 35 ft)
1 PIR coverage pattern

Side View Broad: 11 m x 11 m (35 ft x 35 ft)
1 PIR coverage pattern

2

Look-down zone

Mounting
The recommended mounting height is 2.3 m to 2.7 m
(7.5 ft to 9 ft).
The detector can be mounted:

On a flat wall (surface, semi-flush) with the optional

B335 Swivel-mount Bracket, or with the optional B328

Gimbal-mount Bracket,

In the junction of two perpendicular walls, or

On the ceiling with the optional B338 Ceiling-mount

Bracket.

Note

The use of optional mounting brackets can
reduce the detector's range and increase the
dead zone areas.

Power Considerations
Power Limits
Input power must be provided by an Approved Limited
Power Source. All outputs must be connected to SELV
(safety extra-low voltage) circuits only.
Standby Power
This detector has no internal standby battery. For UL Listed
product installations, 4 hr (40 mAh) of standby power must
be supplied by the control unit or by a UL Listed burglary
power supply.

Parts Included

Quant.

Component

1

Detector

1

Hardware pack

1

Literature pack

Technical Specifications

Environmental Considerations

Designed to comply with EN50131-2-2 Environmental Class II, Security

Grade 2
Relative Humidity:

0 to 85%, non-condensing

Temperature (operating):

-29°C to +49°C (-20°F to +120°F)

For UL Listed product installations,

0°C to +49°C (+32°F to +120°F)

Mechanical Properties

Color:

White

Dimensions:

10.7 cm x 6.1 cm x 4.8 cm (4.2 in. x 2.4 in. x 1.9 in.)

Material:

High-impact ABS plastic

Radio Frequency

Interference (RFI)

Immunity

No alarm or setup on critical frequencies in the range

from 26 MHz to 950 MHz at field strengths less than

50 V/m.

Outputs

Digital Alarm:

5 V normally, grounded for 4 sec during alarm.

Relay:

Solid state, supervised, Form A normally-closed (NC) con-

tacts rated for 125 mA, 28 VDC, 3 W.

Tamper:

Normally-closed (NC) contacts (with cover on) rated at

28 VDC, 125 mA maximum.

Connect tamper circuit to 24-hour protection circuit.

Power Requirements

Current (Alarm):

18 mA

Current (Standby):

10 mA maximum at 12 VDC

Voltage (Operating):

10 VDC to 14 VDC

Ordering Information

ISM‑BLP1 Blue Line PIR Detector

Produces sharply-focused images throughout

the field of view providing superior response

to intruders

ISM-BLP1

Accessories

ISM‑BLA1‑CC Blue Line Color Camera
Module (NTSC format)

NTSC format

ISM-BLA1-CC-N

ISM‑BLA1‑CC Blue Line Color Camera
Module (PAL format)

PAL format

ISM-BLA1-CC-P

ISM‑BLA1‑LM Blue Line Nightlight Module

Fits all Blue Line detectors

ISM-BLA1-LM

ISM‑BLA1‑SM Blue Line Sounder Module

Fits all Blue Line detectors

ISM-BLA1-SM