LSN Peripherals | LSN Expansion Modules | 375

Installation
When installing the KR 100 LSN, the factory-installed solder
distributors must be removed. A maximum of four
KR 100 LSNs can be installed per NVK 100 LSN. One solder
distributor is supplied per two KR 100 LSNs.
Coupler power supply
The LSN part of all LSN elements (couplers and detectors)
is supplied with power via the control panel's 2-wire LSN
line.
All LSN couplers are designed to loop through the power
supply (+V, -V) of subsequent couplers.
The maximum cable length of the separate power supply
(+V, -V) depends on the power intake of the couplers to be
supplied and their peripherals, if not powered by an
external source.
Cable lengths
Cable length per primary line (PL) or control lines

Maximum length unshielded cable – 10 m

Maximum length shielded cable – 500 m

The primary cables, control cables and contact cables from
the NVK 100 may not exceed a total of 500 m per network
processing implementer (NVU).
Optional KR 100 LSN relay module for LSN expanders
The KR 100 LSN relay module for LSN expanders is intended
for use in the NNK 110 LSN and NVK 100 LSN.
The KR 100 LSN is installed if the high power requirement
means the connected control elements cannot be
controlled directly from the LSN couplers, or in order to
enable zero-potential switching.
Up to four KR 100 LSNs can be installed per NNK 110 LSN
or NVK 100 LSN. One solder distributor is supplied per two
KR 100 LSNs.

Parts Included

Type

Qty.

Component

NVK 100 LSN

1

Coupler

Technical Specifications

Operating voltage

LSN part

+10 V to +33 V

Other expansion module func-

tions

+8 V to +30 V

Current consumption
LSN part

3.5 mA

Other expansion module functions

Idle:

Max. 50 mA at +8 V

Max. 40 mA at +12 V

Max. 30 mA at +30 V

Full load:

Max. 315 mA at +8 V

Max. 230 mA at +12 V

Max. 105 mA at +30 V

Connection options

DC primary lines

Primary lines 1 to 4

as hold-up, intrusion, tamper, or clo-

sure zone

Primary line 5

Block-type lock/or coded arming de-

vice

Primary line 6

as hold-up, intrusion, tamper, or clo-

sure zone or for coded arming device

End-of-line resistors

Primary lines 1 to 4

R= 12.1 kilohm 1%

Primary line 5

R = 12.1 kilohm 1% (armed)

R = 12.1 kilohm // 3.92 kilohm

(disarmed)

Primary line 6

(Hold-up, intrusion, tamper,

not with NZ 300)

R = 12.1 kilohm +1%

Primary line 6

(Log. switching equipment)

R = 12.1 kilohm +1%

Invalid coded arming device

12K1 II 3K92 +1%

Valid coded arming device

Monitoring tolerance at

PL 1 to 4 (PL 6 if necessary)

40% of end-of-line resistor (EOL)

Response time PL 1 to 6

< 200 ms

Control outputs

Max. current

20 mA

Max. voltage

8 V

Max. line resistance

2 x 10 Ohm

Short-circuit stability

2 s

Block-type lock magnet

Max. current

60 mA

Max. voltage

12 V

Max. line resistance

2 x 5 Ohm

Short-circuit stability

2 s

Ambient climate

DIN 40040 R14

Permitted ambient temperature

0 °C to +55 °C

Housing

Base

Plastic

Cover

Plastic

Color

RAL 9002 grayish white

Weight

Approx. 450 g

Dimensions (H x W x D)

215 x 160 x 35.5 mm

Protection type

IP 30

Environmental class

II (VdS 2110)

KR 100 optional

Reel

Response voltage

> 7 V

Fall-off voltage

< 1 V

Reel voltage

Max. 14.3 V

Contacts

www.boschsecurity.com

Bosch Security Systems B.V.

6