378 | LSN Peripherals | LSN Expansion Modules

Outputs

Control outputs
Low:

0 to 0.5 V

Imax = 0.1 mA

Active

High:

7 to 9 V

Imax = 0.1 mA

Standby

Note

The MAGS-S active glass break detector, the
EKOM 11 contact-less transmitter and the UP
370 T Matchtec detector are not suitable for
connection to the IC 400 LSN.

Parts Included

Type

Qty.

Component

IC 400 LSN

1

Universal expander

Technical Specifications

Operating voltage

LSN part

+12 V to +33 V

Separate power supply

10.8 V to 30 V

Current consumption

LSN part

3.84 mA

By separate power supply

Max. 20 mA

Inputs/outputs

Inputs

2 differential detector zones

(1 x alarm, 1 x tamper)

Terminating resistance

12 kilohm

Anti-masking/fault

1 input active when 0 V

Tamper contact

Switched internally in series with

tamper input

Outputs

Walk test and alarm memory

Power supply output for connected detectors

I

20 mA

V

9.6 V ± 0.36 _V

Housing

Material

ABS

Color

White, RAL 9002

ambient temperature

-10 °C to +55 °C

Dimensions (H x W x D)

85 x 85 x 28 mm

Protection category

IP 40

Environmental class

II

Ordering Information

IC 400 LSN Universal Expander

For connecting conventional motion detectors

to the local security network LSN

4998110382

Bosch Security Systems B.V.

www.boschsecurity.com

6