1 reading parameters (sdo upload), Reading parameters (sdo upload), 9function library l_iodrvethercat.lib – Lenze EtherCAT Controller-based Automation User Manual

Page 116

Advertising
background image

9

Function library L_IODrvEtherCAT.lib

9.2

CoE Interface

116

Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.2.1.1

Reading parameters (SDO upload)

1. The master sends "Initiate Domain Upload Request".
2. The slave acknowledges the request with a positive response ("Initiate Domain Upload

Response").
In the event of an error the slave responds with "Abort Domain Transfer".

SDO Upload Request
Detailed breakdown of the data for an "SDO Upload Request":

Note!

In the case of jobs for the inverter, please make sure that you convert the code into an

index.

Indexing of the Lenze codes

( 115)

SDO frame area

Data field

Data type / length

Value / description

Mailbox header

Length

WORD

2 bytes

0x0A: Length of the mailbox service data

Address

WORD

2 bytes

Station address of the source if an EtherCAT

master is the instructing party.

Station address of the target if an EtherCAT slave

is the instructing party.

Channel

WORD

6 bits

(0 ... 5)

0x00: Reserved

Priority

2 bits

(6, 7)

0x00: Lowest priority

...

0x03: Highest priority

Type

4 bits

(8 ... 11)

0x03: CANopen over EtherCAT (CoE)

Reserved

4 bits

(12 ... 15)

0x00

CANopen header Number

WORD

9 bits

(0 ... 8)

0x00

Reserved

3 bits

(9 ... 11)

0x00

Service

4 bits

(12 ... 15)

0x02: SDO request

SDO

Reserved

BYTE

4 bits

(0 ... 3)

0x00

Complete access

1 bit

(4)

0x00: The entry addressed with index and

subindex is read.

0x01: The complete object is read. (Currently not

supported.)

Command specifier

3 bits

(5 ... 7)

0x02: Upload request

Index

WORD

2 bytes

Index of the object

Subindex

BYTE

1 byte

Subindex of the object

0x00 or 0x01 if "Complete access" = 0x01.

Reserved

DWORD

4 bytes

0x00