4.1.2.1

The EtherCAT state machine

Before communication via EtherCAT is possible, the fieldbus is scanned by the EtherCAT state

machine when the installation is being powered up. The following illustration shows the possible

status changes from the point of view of an EtherCAT slave.

[4-2]

EtherCAT state machine

E94AYCET009

Operational

Pre-Operational

Init

Safe-Operational

State

Description

Init

• Initialisation phase

• No SDO/PDO communication with the slaves

• Device can be detected by fieldbus scan

Pre-operational

• The fieldbus is active.

• SDO communication (mailbox communication) is possible.

• No PDO communication

Safe-operational

• SDO communication (mailbox communication) is possible.

• PDO communication:

• The input data in the process image are updated.

• The output data from the process image are not transferred to the slaves.

Operational

Normal operation

• SDO communication

• PDO communication

• Fieldbus synchronisation has been successful (if used)

Note!

• A fieldbus scan is possible in any EtherCAT state.

Determining the physical EtherCAT configuration (fieldbus scan)

( 75)

• The SDO communication via the EtherCAT bus is only possible if at least the "Pre-

Operational" state has been reached.

• Only in the transitional phases between states can bus nodes be in different states.