7commissioning of the system – Lenze EtherCAT Controller-based Automation User Manual

Page 79

Advertising
background image

Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17

79

7

Commissioning of the system

7.3

Detailed description of the commissioning steps

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.3.10

Creating a control configuration (adding field devices)

How to create a control configuration in »PLC Designer«

1. Open the context menu of the target system and execute the command

Append

device in order to extend the control configuration with

"EtherCAT Master".

Note!

Before creating an EtherCAT configuration in »PLC Designer«, ensure that the following

conditions have been met:

• The sequence of EtherCAT slaves in the device tree must correspond to the physical

arrangement of the EtherCAT topology.

• SoftMotion operation is only possible with EtherCAT slaves that use the CiA402

application (SM_Drives, e.g. Servo Drives 9400 Highline CiA402).

• Select the cycle times according to the technical data from 1 ... 10 ms.

Advertising