7

Commissioning of the system

7.3

Detailed description of the commissioning steps

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

How to set DC synchronisation:

1. Set the DC cycle time at the master (Lenze Controller) in the Master tab of the EtherCAT

master.

• Select the cycle times according to the technical data from 1 ... 10 ms.
• The (basic) cycle time set here is valid for all Logic and Motion nodes synchronised by

distributed clocks.

• For the Lenze field devices listed in the following table, the indicated settings must be

made by means of the »Engineer«. The Lenze Controller does not write the values into

the slave field devices.

• In the case of the Servo-Inverter i700, all the parameters needed for operation are

stipulated by means of the Lenze Controller (settings in »PLC Designer«).

Commissioning the i700 servo inverter

( 44)

• If the DC setting and the selection of the sync source are inconsistent with each other

(e.g. Servo Drives 9400: C01120 = MXI1 and "DC unused"), the devices cannot be set to

the "Operational" state.

• The settings of the parameters sync cycle time (C01121), sync phase position (C01122),

sync tolerance (C01123) and sync PLL increment (C01124) common for the Lenze system

bus (CAN) cannot be made for EtherCAT. These values are automatically calculated by

the EtherCAT communication module and set internally in the inverter.

Field devices

Settings in »Engineer«

Inverter Drives 8400

• C01120 = 4 (sync source: EtherCAT module in MCI)

Servo Drives 9400

• C01120 = 4 or 5 (sync source: EtherCAT module in MXI1 or MXI2)
• C013892/C14892 = 1 (process data mode = "deterministic mode")

Note!

For Servo Drives 9400 CiA402, C013892/C14892 (process data mode) is defined via

the »PLC Designer«.

See

Start parameters of the Servo Drives 9400 HighLine CiA 402 ( 103)

.