7

Commissioning of the system

7.3

Detailed description of the commissioning steps

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

In the case of field devices shown in green, their position in the physical network matches

the position within the »PLC Designer« configuration. If field devices are shown in red, this

is not the case.
You now have two ways of adapting the »PLC Designer« configuration:

• If you click the Copy all button and then confirm by clicking the OK button, all devices will

be incorporated into the »PLC Designer« configuration.

• You can also incorporate individual devices into the »PLC Designer« configuration or

replace ones already there:

1. Select field device under "Searched devices".

2. Select a device under "Configured devices".

3. Click one of the buttons that are now active: Copy (before), Copy (after) or Replace

with.

Missing device descriptions
If a device available at the fieldbus is not present, an error message within the "Scan Devices" dialog

box will inform you about it:

• The device cannot be interpolated into the project as the corresponding device description has

not been installed.

• In order to install the device in the »PLC Designer«, the suitable device description file is

required. The device identification (Vendor ID, Product Code, Revision) can be helpful to identify

the device (see also Lenze

EtherCAT product codes

( 26)

).

Importing missing devices / device description files

( 78)

Note!

Set up the sequence of devices in the »PLC Designer« project so that it is identical to the

physical sequence in the network. Otherwise, a "bus mismatch" occurs during

downloading.

Note!

The change in the device configuration only comes into effect after renewed translation

of the »PLC Designer«-project:
1. Log out: menu command Online Logout or <Ctrl>+<F8>
2. Translate: menu command Build Build or <F11>
3. Log in: menu command Online Login or <Alt>+<F8>
Only then will all EtherCAT slaves be initialised.