12

Diagnostics

12.5

Error scenarios

178

Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12.5.4

Error during process data transfer

A faulty EtherCAT I/O mapping causes errors during the process data transfer.

Cause

Use of logic addresses

In the »PLC Designer« application, access does not take place symbolically but directly via

the I/O addresses (%Ixx, %Qxx) of the EtherCAT input and output objects and the bus

structure, the PDO selection etc. has have changed.

Error message

-

Remedies

In the »PLC Designer« application, the input and output objects must be accessed via

individual non-ambiguous variables. The variable names must comply with the IEC 61131

syntax (no space characters and leading digits in the variable names).

Example:

Processing EtherCAT I/O mapping ( 95)

Cause

Manual definition of the logic address in the EtherCAT I/O mapping

Example: The address %QB70 has been changed to %QB1000.

Error message

-

Remedies

It is not permissible to manually manipulate the I/O addresses for the EtherCAT bus!