8 shafts do not rotate, 12 diagnostics – Lenze EtherCAT Controller-based Automation User Manual

Page 182

Advertising
background image

12

Diagnostics

12.5

Error scenarios

182

Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12.5.8

Shafts do not rotate

Cause

The EtherCAT bus could not be set to the "Operational" state

The EtherCAT bus does not assume the "Operational" state ( 176)

Error message

-

Remedies

The EtherCAT bus does not assume the "Operational" state ( 176)

Cause

Clicking noise of the shafts after "out-of-sync"

Error during process data transfer ( 178)

Error message

-

Remedies

Error during process data transfer ( 178)

Cause

Faulty SoftMotion scaling/mapping

With SoftMotion scaling/mapping, the increments per revolution are not set.

Error message

-

Remedies

Check the following settings and correct them if required:

• Gearbox ratio in the »PLC Designer« application

• Mapping settings in the master configuration

When the Lenze Controller is started, the complete configuration/PDO mapping is written

into the EtherCAT slaves. When this is done, mapping entries, e.g. from the »Engineer« are

overwritten.

Tip: In the case of the Servo Drive 9400 HighLine Cia402, 65536 increments per revolution

are correct.