7commissioning of the system – Lenze EtherCAT Controller-based Automation User Manual
Page 98
Advertising
![background image](/manuals/565689/98/background.png)
7
Commissioning of the system
7.3
Detailed description of the commissioning steps
98
Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2. Activate the expert settings on the Slave tab of the slave drive.
The Expert Process Data tab appears next to the Slave tab:
3. Open the Expert Process Date tab.
4. Double-click the free PDO mapping (16#1605) in the PDO list.
5. In the dialog box that appears, process the free PDO mapping and close the dialog box by
clicking the OK button.