7commissioning of the system – Lenze EtherCAT Controller-based Automation User Manual
Page 80

7
Commissioning of the system
7.3
Detailed description of the commissioning steps
80
Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2. Append the EtherCAT slaves under the EtherCAT master.
You have two options:
• Automatically
Determining the physical EtherCAT configuration (fieldbus scan)
(previously:
Configuring the communication parameters
• Manually with the command
Append device in the context menu of the EtherCAT
master
Select a field device from the
selection list. Only those devices can be selected whose
EtherCAT device descriptions have been imported in »PLC Designer«.
Importing missing devices / device description files
Repeat the command
Append device until all participating slaves on the field bus have
been incorporated in the EtherCAT configuration.