12 diagnostics, 6 system error messages 184 – Lenze EtherCAT Controller-based Automation User Manual

Page 184

Advertising
background image

12

Diagnostics

12.6

System error messages

184

Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

0x98110015

ETC_E_UNKNOWN_MBX_PROTOCOL

Unknown mailbox protocol

Mailbox command ID with unknown protocol assignment

Internal error. Please contact Lenze.

0x98110016

ETC_E_ACCESSDENIED

Access denied (internal software error on the master)

Internal error. Please contact Lenze.

0x9811001A

ETC_E_PRODKEY_INVALID

The evaluation version of the master is used. The master enters the "Stop" mode

after 30 minutes.

Internal error. Please contact Lenze.

0x9811001B

ETC_E_WRONG_FORMAT

The XML file contains no or faulty content.

Internal error. Please contact Lenze.

0x9811001C

ETC_E_FEATURE_DISABLED

Attempt to execute a non-existing or deactivated function.

Internal error. Please contact Lenze.

0x9811001D

ETC_E_SHADOW_MEMORY

The shadow memory has been requested in wrong mode.

Internal error. Please contact Lenze.

0x9811001E

ETC_E_BUSCONFIG_MISMATCH

The EtherCAT configuration of the master and the connected slaves does not

comply with the physical bus structure.

0x9811001F

ETC_E_CONFIGDATAREAD

The XML file cannot be read.

Internal error. Please contact Lenze.

0x98110021

ETC_E_XML_CYCCMDS_MISSING

The XML file of the master does not contain any cyclical commands.

Internal error. Please contact Lenze.

0x98110022

ETC_E_XML_ALSTATUS_READ_MISSING

The XML file of the master does not contain the command for reading the AL

Status Register.

Internal error. Please contact Lenze.

0x98110023

ETC_E_MCSM_FATAL_ERROR

The master state machine is in an invalid state.

Internal error. Please contact Lenze.

0x98110024

ETC_E_SLAVE_ERROR

The slave cannot be addressed.

0x98110025

ETC_E_FRAME_LOST

An EtherCAT frame was lost on the fieldbus, i.e. it has not been received. If this

error occurred frequently, this indicates the wiring may be faulty.

0x98110026

ETC_E_CMD_MISSING

The received EtherCAT frame is not complete.

Internal error. Please contact Lenze.

0x98110028

ETC_E_INVALID_DCL_MODE

This function cannot be used when DC latching is in the "Auto Read" operating

mode.

Internal error. Please contact Lenze.

0x98110029

ETC_E_AI_ADDRESS

The connected slaves do not comply with the control configuration. This error

only occurs if a previously existing slave disappears.

Internal error. Please contact Lenze.

0x9811002A

ETC_E_INVALID_SLAVE_STATE

The mailbox commands are not permissible in the current slave state.

0x9811002B

ETC_E_SLAVE_NOT_ADDRESSABLE

The slave has been switched on/off.

0x9811002C

ETC_E_CYC_CMDS_OVERFLOW

Error during XML file creation by the configurator

Internal error. Please contact Lenze.

0x9811002D

ETC_E_LINK_DISCONNECTED

The EtherCAT cable has not be connected/plugged into the Lenze controller.

0x9811002E

ETC_E_MASTERCORE_INACCESSIBLE

The connection to the master (server) is interrupted or the master has been

stopped.

Internal error. Please contact Lenze.

0x9811002F

ETC_E_COE_MBXSND_WKC_ERROR

It is not possible to write to the CoE mailbox in the slave. The slave has not yet

read the mailbox.

Internal error. Please contact Lenze.

0x98110030

ETC_E_COE_MBXRCV_WKC_ERROR

It is not possible to read the CoE mailbox in the slave.

Internal error. Please contact Lenze.

0x98110031

ETC_E_NO_MBX_SUPPORT

The slave does not support mailbox transfer.

0x98110032

ETC_E_NO_COE_SUPPORT

Configurator error or the slave description file does not correspond with the

slave firmware.

0x98110033

ETC_E_NO_EOE_SUPPORT

Configurator error or the slave description file does not correspond with the

slave firmware.

0x98110034

ETC_E_NO_FOE_SUPPORT

Configurator error or the slave description file does not correspond with the

slave firmware.

0x98110035

ETC_E_NO_SOE_SUPPORT

Configurator error or the slave description file does not correspond with the

slave firmware.

Is not supported.

0x98110036

ETC_E_NO_VOE_SUPPORT

Configurator error or the slave description file does not correspond with the

slave firmware.

Is not supported.

Error no.

[hex]

Designation

Description

Advertising