2.4.34.1

Enable of the FIXSET1 setpoints

Number of required fixed setpoints

Number of the inputs to be assigned

1

at least 1

1 ... 3

at least 2

4 ... 7

at least 3

8 ... 15

4

Decoding table of the binary input signals:

Output signal
FIXSET1−OUT =

1st input

FIXSET1−IN1

2nd input

FIXSET1−IN2

3rd input

FIXSET1−IN3

4th input

FIXSET1−IN4

FIXSET1−AIN

0

0

0

0

C0560/1

1

0

0

0

C0560/2

0

1

0

0

C0560/3

1

1

0

0

C0560/4

0

0

1

0

C0560/5

1

0

1

0

C0560/6

0

1

1

0

C0560/7

1

1

1

0

C0560/8

0

0

0

1

C0560/9

1

0

0

1

C0560/10

0

1

0

1

C0560/11

1

1

0

1

C0560/12

0

0

1

1

C0560/13

1

0

1

1

C0560/14

0

1

1

1

C0560/15

1

1

1

1

0 = LOW

1 = HIGH