Cw/ccw/quick stop (r/l/q), Configuration, 53 cw/ccw/quick stop (r/l/q) – Lenze EVF9383 User Manual

Page 161: Function

Advertising
background image

Configuration

2−153

l

EDSVF9383V−EXT EN 2.0

2.4.53

CW/CCW/Quick stop (R/L/Q)

This FB evaluates the input of the direction of rotation protected against wire breakage. If there is no
signal for the direction of rotation, quick stop is released.

C0889/2

C0889/1

R/L/Q

R/L/Q−QSP

R/L/Q−R/L

R/L/Q−R

R/L/Q−L

C0885

C0886

Fig. 2−131

CW/CCW/Quick stop (R/L/Q)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

R/L/Q−R

d

C0889/1

bin

C0885

2

51

R/L/Q−L

d

C0889/2

bin

C0886

2

52

R/L/Q−QSP

d

R/L/Q−R/L

d

Function

l

After mains connection, the two outputs are initialized as follows:

Inputs

Outputs

R/L/Q−R

R/L/Q−L

R/L/Q−R/L

R/L/Q−QSP

0

1

0 = LOW

1 = HIGH

l

After the initialization, the following relationship results in dependence of the input signals:

Inputs

Outputs

R/L/Q−R

R/L/Q−L

R/L/Q−R/L

R/L/Q−QSP

0

0

0/1

*

1

1

0

0

0

0

1

1

0

1

1

unchanged

unchanged

0 = LOW

1 = HIGH

*

If you have selected a direction of rotation and then set both inputs to LOW, the signal state at R/L/Q−R/L will not change.

Advertising