Configuration

Use of funktion blocks

2−36

l

EDSVF9383V−EXT EN 2.0

Basic procedure

1. Select the configuration code of the function block input to be changed.

2. Where do you want the input signal for the selected input to come from?

(e.g. from the output of another function block).

3. A menu which only contains signal sources of the same type as the function block input to be

assigned is used to assign the function block input.

4. Select and confirm the signal source.

5. Remove connections that are not desired, if necessary.

– For this, use the configuration code and select a corresponding input signal assignment

(e. g. FIXED0, FIXED1, FIXED0%, ...).

6. Repeat steps 1 to 5 until the desired configuration has been created.

7. Save the new configuration in the desired parameter set.

Example

l

Condition:

– Default setting

l

Task:

– Square the analog signal of X6/3, X6/4 and output it at X6/62.

l

Solution:

– You need the function blocks AIN2, ARIT2 and AOUT2.

+ −

*

/

x/(1−y)

C0600

x
y

ARIT2

ARIT2−OUT

C0602/1

"200%

C0602/2

ARIT2−IN1

ARIT2−IN2

C0601/1

C0601/2

62

AOUT1

C434/1

+

+

AOUT1−IN

AOUT1−GAIN

AOUT1−OFFSET

C0434/3

C0434/2

C0431

C0433

C0432

3
4

AIN2

+

+

AIN2−OUT

AIN2−GAIN

AIN2−OFFSET

C0409/1

C0409/2

C0407

C0408

C0108/1

C0109/1

C0027/2

C0026/2

Fig. 2−17

Example of a simple configuration