Commissioning

The commissioning should be carried out with motors without any load.

1. Start the drive with a LOW−HIGH transition at X5/E5.

2. Setting the acceleration time T

ir

:

– Set the speed setpoint to 100 %, operate the controller with maximum speed.

– Inhibit the controller via terminal X5/28 (you can also use any other source for the controller

inhibit, CINH ) and measure the deceleration time to standstill.

– Set approx. 1/10 of the deceleration time under C0982.

3. Setting the retrigger time

l

For mains failure detection by detecting the DC−bus voltage level:

– Under C0983, set the deceleration time measured under point 2..

l

For mains failure detection via an external system (e.g. 934X supply module):

– Under C0983, set the time for which the drive continues to be braked in a controlled way in

the event of a short−term mains recovery.

4. Switch off the supply voltage (mains or DC bus).

– The oscilloscope should display the following sequence:

U G

t 1

t 2

Q

t

n

0

0

M F A I L - D C - S E T

t

R

S

T

Fig. 2−97

Schematic representation with activated mains failure control (ideal characteristic)
 Switch−off threshold OU
‚ Switch−on threshold for brake unit
ƒ Switch−off threshold LU
„ Threshold CMP2−OUT
t1

Mains failure

t2

Zero speed reached