Configuration

2−148

l

EDSVF9383V−EXT EN 2.0

l

C0329 = 2

– The input of gain V

p

is derived from the process setpoint PCTRL1−SET. The setpoint is

obtained after the ramp generator and calculated via the characteristic with three
co−ordinates.

V

p

V

p1

V

p2

V

p3

s

s

0

s

1

Input data:
V

p1

= C0222

V

p2

= C0325

V

p3

= C0326

s

0

= C0328

s

1

= C0327

Display value:
V

pact

= C0336

Fig. 2−124

The input of gain V

p

is derived from the process setpoint PCTRL1−SET

l

C0329 = 3

– The input of gain V

p

is derived from the control difference and led via the characteristic

generation as C0329 = 2.

Gain V

p

for PCTRL2

The gain V

p

is entered under C1332.

2.4.50.2

Ramp generator

The setpoint PCTRLx−SET is led by a ramp generator with linear characteristic. Thus, setpoint
step−changes at the input can be transformed into a ramp.

100 %

0

tir

tif

Tir

Tif

t

RFG−OUT

[%]

w1

w2

T

ir

+ t

ir

100%

w2

* w1

T

if

+ t

if

100%

w2

* w1

Fig. 2−125

Acceleration and deceleration times of the ramp generator

Set ramps for acceleration and deceleration

Reset ramp generator
(the ramp generator is set to 0)

Acceleration time t

ir

Deceleration time t

if

PCTRL1

C0332

C0333

PCTRL1−INACT = HIGH

PCTRL2

C1330

C1331

PCTRL2−INACT = HIGH