Configuration, Basic configuration – Lenze EVF9383 User Manual

Page 37

Advertising
background image

Configuration

Basic configuration

2−29

l

EDSVF9383V−EXT EN 2.0

Code

Lenze setting

Explanation

C1300

Motor speed at D

max

, function block DCALC1

500 rpm

C1301

Maximum line speed, function block DCALC1

2500 rpm

C1302

Calculation cycle, function block DCALC1

0.1 rev

C1303

Filter time constant, function block DCALC1

1.00 s

C1304

Maximum diameter, function block DCALC1

500 mm

C1305

Lower diameter limit, function block DCALC1

100 mm

C1306

Upper diameter limit, function block DCALC1

500 mm

C1307

Hysteresis − diameter limitation, function block DCALC1

1.00 %

C1308

Selection of the arithmetic function, function block DCALC1

1

C1309

Minimum diameter, function block DCALC1

100 mm

C1310

Acceleration and deceleration time, function block DCALC1

1.000 s

C1311

Permissible diameter difference, function block DCALC1

1.00 %

C1328

Display of current diameter, function block DCALC1

0 mm

C0105

Quick stop deceleration time

5.00 s

C0640

Time constant, function block PT1−1

1.00 s

C0685

Comparison function, function block CMP2

1

C0686

Hysteresis for input signals, function block CMP2

1.00 %

C0687

Window for signal comparison, function block CMP2

1.00 %

C0720

Function, function block DIGDEL1

2

C0721

Delay time, function block DIGDEL1

0.100 s

C0950

Numerator for digital frequency evaluation

5

C0951

Denominator for digital frequency evaluation

1

C0017

Q

min

switching threshold

50 rpm

)

Note!

In this configuration, incremental encoder input X8 can be activated by selecting
output input signal at X8 (C0540 = 5) for digital frequency output X10.