Configuration – Lenze EVF9383 User Manual

Page 146

Advertising
background image

Configuration

2−138

l

EDSVF9383V−EXT EN 2.0

2.4.47.3

Setpoint inversion

The output signal of the JOG function is led via an inverter.

The sign of the setpoint is inverted, when the input NSET−N−INV = HIGH.

2.4.47.4

Ramp function generator for the main setpoint

The setpoint is then led via a ramp function generator with a linear characteristic. The ramp function
generator converts setpoint jumps at the input into a ramp.

100 %

0

tir

tif

t ir

t if

t

RFG−OUT

[%]

w1

w2

T

ir

+ t

ir

100%

w2

* w1

T

if

+ t

if

100%

w2

* w1

Fig. 2−113

Acceleration and deceleration times of the ramp function generator

l

The acceleration and deceleration ramps can be separately selected.

– Via the inputs NSET−TI*x 16 you can activate different acceleration and deceleration times

(see JOG setpoints, table and function. The decoding is made according to the signal plan).

– The T

i

times can only be activated in pairs.

l

When the controller inhibit (CINH) is set, the ramp function generator accepts the value at the
input NSET−CINH−VAL and passes it on to the following function. This function has priority
over all other functions.

l

NSET−RFG−STOP = HIGH

– The ramp function generator is stopped. Changes at the input of the ramp function

generator have no effect on the output signal.

l

NSET−RFG−0 = HIGH

– The ramp function generator decelerates to zero along its deceleration ramp.

l

It is also possible to load the ramp function generator in advance with a value. For this, the
input NSET−LOAD must be set = HIGH. As long as this input is set, the value at the input
NSET−SET is accepted by the ramp function generator and provided at the output.

Advertising
This manual is related to the following products: